ABB REF 610 Technical Reference Manual page 60

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
Switch
Function
SGF5/7
Selection of the latching feature for programmable LED7
SGF5/8
Selection of the latching feature for programmable LED8
When the switch is in position 0 and the signal routed to the LED is reset, the programmable
*
LED is cleared.
When the switch is in position 1, the programmable LED remains lit although the signal
*
routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI, a digital input or the serial bus.
ΣSGF5
Table 5.1.4.10.-7
SGB1...SGB5
Switch
Function
SGB1...5/1
0 = indications are not cleared by the digital input signal
*
1 = indications are cleared by the digital input signal
*
SGB1...5/2
0 = indications are not cleared and latched output contacts are not unlatched by the digital
*
input signal
1 = indications are cleared and latched output contacts are unlatched by the digital input
*
signal
SGB1...5/3
0 = indications and memorized values are not cleared and latched output contacts are not
*
unlatched by the digital input signal
1 = indications and memorized values are cleared and latched output contacts are unlatched
*
by the digital input signal
SGB1...5/4
Switching between setting groups 1 and 2 by using the digital input
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input. When the digital input is energized,
*
setting group 2 is activated, if not, setting group 1 is activated.
SGB1...5/5
Time synchronization by the digital input signal
SGB1...5/6
External tripping by the digital input signal
SGB1...5/7
External triggering of the CBFP by the digital input signal
SGB1...5/8
External triggering of the trip lockout by the digital input signal
SGB1...5/9
External arc signalling by the digital input signal
SGB1...5/10
Resetting of the trip lockout by the digital input signal
SGB1...5/11
Blocking of tripping of stage I> by the digital input signal
SGB1...5/12
Blocking of tripping of stage I>> by the digital input signal
SGB1...5/13
Blocking of tripping of stage I
SGB1...5/14
Blocking of tripping of stage I
Blocking of tripping of stage ΔI> by the digital input signal
SGB1...5/15
SGB1...5/16
External AR inhibition by the digital input signal
SGB1...5/17
External inhibition of CB reclosing by the digital input signal
60
Feeder Protection Relay
Technical Reference Manual
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
When SGB1...5/4 is set to 1, it is important that the switch has the same setting
in both setting groups.
> by the digital input signal
0
>> by the digital input signal
0
1MRS755310
Default setting
0
0
0
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0