1MRS755310
Table 5.1.4.10.-12 SG3
Switch
Function
SG3/1
Inhibition of the AR function by the trip signal from stage I>>>
SG3/2
Ihibition of the AR function by the trip signal from stage I
Inhibition of the AR function by the alarm signal from stage θ>
SG3/3
Inhibition of the AR function by the trip signal from stage ΔI>
SG3/4
*
SG3/5
Resetting indications at CB reclosing
*
ΣSG3
Feeder Protection Relay
Technical Reference Manual
When the switch is in position 1, the AR function is inhibited.
When the switch is in position 1, indications are reset when the AR function
issues a reclosing command to the circuit breaker.
New trip indication timer
The new trip indication timer can be configured to allow a second trip indication on
the LCD. When several protection stages trip, the first trip indication is displayed
until the time, as specified by the NEW TRIP IND. setting value, has expired. After
this, a new trip indication can displace the old one. The basic protection functions
are not affected by the NEW TRIP IND. setting.
Table 5.1.4.10.-13 New trip indication timer
Setting
Description
New trip
New trip indication timer in minutes
indication
No new trip indication allowed until the
previous one has been manually
cleared.
Non-volatile memory settings
Non-volatile memory is backed up by a battery; the battery must be
inserted and charged.
The table below presents data which can be configured to be stored in the non-
volatile memory. All of the functions mentioned below can be selected separately
with switches 1...5 either via the HMI or the SPA bus.
Table 5.1.4.10.-14 Memory settings
Setting
Switch Function
Non-volatile
memory settings
1
0 = operation indication messages and
*
LEDs are cleared
1 = operation indication messages and
*
LEDs are retained
2
1 = disturbance recorder data is retained
*
3
1 = event codes are retained
*
Default setting
>>
0
Setting range
0...998
999
Default setting
a)
a)
a)
REF 610
REF 610
1
1
1
1
0
15
Default setting
60
-
1
1
1
65