ABB REF 610 Technical Reference Manual page 127

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS755310
Description
Default variation of counter
objects
Default variation of counter
change event objects
Default variation of frozen
counter objects
Class 1 event delay
Class 1 event count
Class 2 event delay
Class 2 event count
Class 3 event delay
Class 3 event count
Unsolicited reporting mode
Scaling factor 1
Scaling factor 2
Scaling factor 3
Scaling factor 4
Scaling factor 5
Baud rate
Number of stop bits
Parity
Silent interval
Time slot width
Number of time slots
Collision detection enabled
DNP module warning
register
DNP module status
register
Feeder Protection Relay
Technical Reference Manual
SPA
R, W
Value range
parameter
(channel 503)
503V13
R, W
1...2
503V14
R, W
1, 2, 5, 6
503V30
R, W
1, 2, 5, 6
503V18
R, W
0...255 s
503V19
R, W
0...255
503V20
R, W
0...255 s
503V21
R, W
0...255
503V22
R, W
0...255 s
503V23
R, W
0...255
503V24
R, W
0 = UR disabled
1 = immediate
2 = empty UR
3 = empty UR and
enable UR
503V101
R, W
0...4294967295
503V102
R, W
0...4294967295
503V103
R, W
0...4294967295
503V104
R, W
0...4294967295
503V105
R, W
0...4294967295
503V211
R, W
4.8/9.6/19.2/38.4
503V212
R, W
1...2
503V230
R, W
0 = no parity
1 = odd
2 = even
503V232
R, W
0...65535 ms
503V233
R, W
0...255 ms
503V234
R, W
0...255
503V235
R, W
0 = disabled
1 = enabled
503V168
R
Bit coded
0 = OK
503V169
R
Bit coded
0 = OK
Default Explanation
2
2
2
0
1
0
1
0
1
0
Refer to Unsolicited reporting start up in
Section 5.1.16.4. Specific DNP features.
1
1
1
1
1
9.6
1
0
20
10
8
0
REF 610
REF 610
127

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents