ABB REF 610 Technical Reference Manual page 56

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
REF 610
Table 5.1.4.10.-1
Setting values
Setting
Description
I>/I
Start value of stage I>
n
t>
Operate time of stage I>
IDMT I>
Time/current characteristic for stage
I>
k
Time multiplier k
n
Time multiplier n
t
>
Resetting time of stage I>
r
I>>/I
Start value of stage I>>
n
t>>
Operate time of stage I>>
I>>>/I
Start value of stage I>>>
n
t>>>
Operate time of stage I>>>
I
>/I
Start value of stage I
0
n
t
>
Operate time of stage I
0
IDMT I
>
Time/current characteristic for stage
0
I
>
0
k
Time multiplier k
0
n
Time multiplier n
0
t
Resetting time of stage I
0r>
I
>>/I
Start value of stage I0>>
0
n
t
>>
Operate time of stage I
0
ΔI>
Start value of stage ΔI>
Operate time of stage ΔI>
t
>
Δ
I
Full load current
θ
Time constant of stage θ>
T
θ
Alarm level of stage θ>
>
a
CBFP
Operate time of CBFP
0→1
Number of AR shots
ArcI>
Current limit ArcI> of stage ARC
ArcI
>
Current limit ArcI
0
56
Feeder Protection Relay
Technical Reference Manual
Switching between setting groups via a digital input has a higher
priority than via the HMI or with the parameter V150.
The setting values can be altered via the HMI or with a PC provided with Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read
with the relay trip circuits disconnected or tested with current injection; refer to
Section 8. Check lists for additional information.
Setting range
0.30...5.00 x I
0.05...300 s
0...9
0.05...1.00
1.0...15.0
0.05...2.50 s
0.50...35.0 x I
0.04...300 s
0.50...35.0 x I
0.04...30.0 s
>
1.0...100% I
0
>
0.05...300 s
0
0...9
0.05...1.00
0
1.0...15.0
0
>
0.05...2.50 s
0
5.0...800% I
>
0.05...300 s
0
10...100%
1...300 s
0.30...1.50 x I
1...200 min
50...100% θ
0.10...60.0 s
0 = AR is not in use
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
0.50...35.0 x I
> of stage ARC
5.0...800% I
0
Default setting
0.30 x I
n
0.05 s
0
0.05
1.0
0.05 s
0.50 x I
n
0.04 s
0.50 x I
n
0.04 s
1.0% I
n
0.05 s
0
0.05
1.0
0.05 s
5.0% I
n
0.05 s
100 %
60 s
0.30 x I
n
1 min
95% θ
>
t
0.10 s
0
2.50 x I
n
20.0% I
n
1MRS755310
n
n
n
n
n
n
>
t
n
n