Top Vent - Horizontal Termination
Note: For every 1 ft. of vertical drop
the total allowable length must be
reduced by 2 ft.
WARNING! Risk of Fire! Minimum 2 ft. straight vertical DVP pipe directly off appliance followed by 90 degree
elbow and DVP-2SL adapter on these models:
ESCAPE-42DV, ESCAPE-36DV, ESC-42ST, HEIR36, HEIR42, HEIR50, LUX36, LUX42, TRUE-36, TRUE-42,
TRUE-50, CERONA-36, CERONA-42, MEZZO36, MEZZO36ST, MEZZO48, MEZZO48ST, CRAVE4836, CRAV-
E4836ST, CRAVE6048, CRAVE6048ST, CRAVE7260, CRAVE7260ST, CRAVE8472, CRAVE8472ST, MEZZO60,
MEZZO60ST, MEZZO72, MEZZO72ST, MARQ36IN, MARQ42IN, MARQ42STIN, ECHEL36IN, ECEL36STIN,
ECHEL48IN, ECHEL48STIN, ECHEL60IN, ECHEL72IN, ODFORTG-36, ODMEZG-36
Combustibles surrounding pipe may overheat.
Minimum Vent Run
A minimum of 2 ft. of vertical piping is
required between the appliance and the
PVLP-SLP with certain appliance mod-
els. See Table 2.1.
Figure 2.2 Horizontal PVLP Orientation
7
Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP) Instructions • 4052-900 Rev. M• 09/17
H
2
V
2
A DVP-2SL or DVP-SLP24
is required in any position
after the first 90 degree
elbow on certain models.
See Table 2.1.
See Chart in Section 2.C: "Venting Length - Model Categories and
Length Requirements by Termination Type."