Hearth and Home Technologies PVLP-SLP Installation Instructions Manual page 6

Power vent low profile
Table of Contents

Advertisement

PART NUMBER
DVP-SLP24
DVP-2SL
DIRECT VENT WITH 4 in./ 6-5/8 in. DIAMETER SLP PIPE
MAX. ELBOWS
(45° & 90°)
12-45° or 6-90°
MAX. ELBOWS
(45° & 90°)
12-45° or 6-90°
Note: For every 1 ft. of vertical drop the total
allowable length must be reduced by 2 ft.
NOTE: Maximum total vent run= Total vertical vent run + Total horizontal vent run
NOTICE: If a a pipe configuration includes
a vertical component that goes downward,
a vertical component going back upward is
not allowed.
6
Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP) Instructions • 4052-900 Rev. M• 09/17
Adapts from 5 in./ 8 in. DVP-series starting collars to 4 in./ 6-5/8 SLP-series vent pipe.
Adapts from 5 in./ 8 in. DVP-series starting collars to 4 in./ 6-5/8 SLP-series vent pipe.
MAX. TOTAL VENT
*only allowed on certain
See chart in Section 2.C
DIRECT VENT WITH 5 in. / 8 in. DIAMETER DVP PIPE
MAX. TOTAL VENT
*only allowed on certain
See chart in Section 2.C
MAXIMUM
VERTICAL
DROP
FROM
APPLIANCE
ADAPTER KITS
PART DESCRIPTION
RUN (FT.)
100'
models
RUN (FT.)
100'
models
Note: See the
MAX. VERT.
PRIMO install
DROP (FT.)
manual (2310-970)
for allowed vent
configurations for
12'
the following SKUs:
PRIMO48
PRIMO60
PRIMO72
PRIMO48ST
PRIMO60ST
MAX. VERT.
PRIMO72ST
DROP (FT.)
12'
MAXIMUM
VERTICAL
DROP