Operating Instructions; Installation Inspection; Setting The Pvlp-Slp Baffle Adjustment; Power Vent Operating Instructions - Hearth and Home Technologies PVLP-SLP Installation Instructions Manual

Power vent low profile
Table of Contents

Advertisement

5

Operating Instructions

A. Installation Inspection
1. Follow safety inspection procedures recommended by
national, provincial, and/or local codes.
2. Be certain all electrical connections are properly made
and secure.
3. Visually inspect the vent system and determine that
there is no flue gas spillage, blockage or restriction,
leakage, corrosion or other unsafe deficiencies.
CAUTION! Risk of electrical shock! DO NOT allow
120VAC wires to contact hot metal surfaces. Use sup-
plied wire ties to bundle wires away from flue pipe, fan
housing and other metal surfaces.
B. Setting the PVLP-SLP Baffle Adjustment
Note
: The air baffle may be adjusted after installation.
The baffle adjustment screw can be accessed by remov-
ing the front cap cover.
CAUTION! Risk of overheating! The baffle must remain
fully closed when using PVLP-SLP with PRIMO models.
• If the burner flames are short, active, and jumping – turn
the bolt counter-clockwise (open). Check the burner
flames and adjust the baffle again as necessary until the
flames are stable, strong, and steady.
• If the burner flames are tall, lifting, floating, and ghost-
like, the baffle is too open and MUST be closed (turn bolt
clockwise).
• If the pilot continously sparks and does not become
steady, the baffle may need to be opened. The
requirements in Table 5.1 must still be met.
Distance from PVLP-SLP to
Appliance
2-15 ft.
16-39 ft.
Greater than 40
Table 5.1.
28
Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP) Instructions • 4052-900 Rev. M• 09/17
Maximum Allowable
Baffle Setting
2.5 in. open
1.5 in. open
Closed
C. Power Vent Operating Instructions
After installation of the power vent, follow the operation
instructions below for the type of control system/remote
control used (IPI Plus/RC300, IFT/RC400/RC150.
IPI Plus/RC300
1. Turn the remote "ON".
Note
: During the period of operation after turning the
fireplace "ON", there will be a delay (approx. 120 seconds)
before the fireplace ignites. This is due to the time neces-
sary for the fan to reach operating speed and to remove
any gases from the combustion chamber.
2. After turning the remote to the "ON" position, if the fire-
place does not turn on, turn the remote to "OFF" refer
to the troubleshooting section.
3. Turn the remote to "OFF" to turn off the burner. The
power vent will continue to run for 20 minutes.
IFT/RC400
1. Touch screen on RC400 to wake up.
2. Touch 'Turn Flame On'.
3. Observe touch screen - if system is configured properly
for Power Vent Operation, a 2 min countdown timer will
be displayed next to 'Turn Flame OFF'. See Figure
below.
CORRECT PV DISPLAY
If RC400 display is incorrect, touch 'Turn Flame OFF'
and refer to troubleshooting section.
4. If the RC400 display is correct, the Power Vent will be
running and the 2-minute countdown timer will run, after
which the pilot will ignite followed by the main burner.
5. Touch 'Turn Flame OFF' on the RC400. The pilot and
main will extinguish. The Power Vent will continue to
run for 20 min.
WARNING! After installation of Power Vent
components, the RC400 and IFT-ECM MUST BE
Re-Paired for safe operation.
INCORRECT PV DISPLAY