The length of the communication cable must be less than 10 meters. If it is longer than
10 meters, please contact service personnel.
Do not put beverage containers on the UPS, battery cabinet or any other accessory asso-
ciated with the UPS.
The risk of dangerous high voltage is possible when the batteries are still connected to
the UPS even though the UPS is disconnected from the mains. Do not forget to pull out
the battery cable to completely cut off the battery source.
Do not open or mutilate the battery or batteries. The released electrolyte is harmful to the
skin and eyes and may be toxic.
ing or removing the cover of the UPS to avoid high voltage electric shock.
1. Liquid is poured or splashed on the UPS.
2. The UPS does not run normally after this User Manual is carefully observed.
1.4

Storage Warnings

Prior to Installation
If the UPS needs to be stored prior to installation, it should be placed in a dry area. The
allowable storage temperature is between -15°C and +50°C.
After Usage
Press the OFF key (
turn off the UPS, please press the DOWN key (
disconnect the UPS from the utility power, remove all equipment from the UPS, and store
the UPS in a dry and well-ventilated area at a temperature between -15°C and +50°C.
Idle batteries must be re-charged fully approximately every three months if the UPS
needs to be stored for an extended period of time. The charging time must not be less
than 24 hours each time.
Ultron HPH Series UPS
NOTE:
If you use the UPS in an area that generates or incurs dust, you should install a dust
) once and the LCD shows the following screen. If you want to
?
2
). Make sure the UPS is shutdown,
-