Modbus Application Settings - Siemens SITRANS F M MAGFLO series Operating Manual

Modbus rtu rs-485 add-on module for usm ii transmitters
Hide thumbs Also See for SITRANS F M MAGFLO series:
Table of Contents

Advertisement

Modbus RTU RS-485
6.3 Modbus application
settings
6.
Modbus holding registers
Slave ID
Modbus
Modbus
register
address
4:00601
600
4:00602
601
4:00603
602
4:00604
603
4:00606
605
4:00607
606
4:00608
607
4:00614
613
4:00623
622
TAG
Modbus
Modbus
register
address
4:00641
640
Modbus module version
Modbus
Modbus
register
address
4:00650
649
4:00660
659
Modbus error reporting
Modbus
Modbus
register
address
4:00681
680
4:00682
681
4:00683
682
4:00684
683
SFIDK.PS.023.D2.02
No. of
Data
Description
bytes
type
Slave ID: 0x2A = Siemens
2
Byte
2
Byte
Run indicator:
0x00 = not running
0xFF = running
Product code:
2
Byte
24 = MAG 6000
25 = MASS 6000
3
Byte array
Capability bits
2
Word
Flowmeter revision:
e.g. 0x0201 = v2.01
Modbus revision:
2
Word
e.g. 0x0201 = v2.01
12
String
Manufacturer name
18
String
Product name
12
String
Modbus module name
No. of
Data
Description
bytes
type
18
String
TAG
No. of
Data
Description
bytes
type
20
String
Modbus module SW version:
e.g. „1.00"
2
Byte
Modbus module HW version:
e.g. „2"
No. of
Data
Description
bytes
type
2
word
Last Coil Error (CoilAddr)
(Modbus cmd: 1 or 5)
2
word
Last Coil Error (ErrorNo)
(See appendix E)
2
word
Last HoldReg Error
(HoldReg Addr)
(Modbus cmd: 3 or 16)
2
word
Last HoldReg Error (ErrorNo)
(See appendix E)
Read/
write
R
R
R
R
R
R
R
R
R
Read/
write
R/W
Read/
write
R
R
Read/
write
R
R
R
R
15

Hide quick links: