4-Point Characteristic - Samson TROVIS 5579 Mounting And Operating Instructions

Automation system trovis 5500. heating and district heating controller
Table of Contents

Advertisement

Functions of the heating circuit

5.1.2 4-point characteristic

The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points each for the Outdoor temperature , the Flow temperature, the Reduced
flow temperature and the Return flow temperature . The Max. flow temperature and Min. flow
temperature parameters mark the upper and lower limits of the flow temperature.
t
[°C]
VL
100
t
90
VLmax
80
70
60
50
40
P4
30
t
20
VLmin
10
20
15
Fig. 6 · 4-point characteristic
Note: The Day set point and Night set point parameters are no longer available when the
4-point characteristic has been selected, provided no additional functions (e.g. Optimiza-
tion, Flash adaptation) have been selected.
Function
4-point characteristic
Parameters
Outdoor temperature
Flow temperature
72
EB 5579 EN
P2
P3
10
5
0
–5
Point 1
Point 2
Point 3
Point 4
Point 1
Point 2
Point 3
Point 4
P1 to P4
t VL
t A
P1
... min
...max
t
A
–10
–15 –20
[°C]
WE
Configuration
0
CO1, 2, 3 -> F11 - 1
WE
Parameter level / Range of values
–15 °C
PA1, 2, 3 / –30 to 50 °C
–5 °C
5 °C
15 °C
70 °C
PA1, 2, 3 / 5 to 130 °C
55 °C
40 °C
25 °C
Points 1 to 4
Flow temperature
Outdoor temperature
Min. t VL
Max. t VL
4-point characteristic
Reduced 4-point characteristic