Condensate Accumulation Control - Samson TROVIS 5579 Mounting And Operating Instructions

Automation system trovis 5500. heating and district heating controller
Table of Contents

Advertisement

Note: If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity
settings are locked.
Functions
Return flow sensors RüF1/2/3
Return flow temperature
limitation with P algorithm
Parameters
Gradient, return flow
Level, return flow
Return flow temperature foot
Max. return flow temperature
Max. return flow temperature
or
Return flow temp. points 1 to 4
Note: To ensure that the preset return flow temperature limiting can be met, make sure that
– the heating characteristic is not adjusted to ascend too steeply,
– the speed of the circulation pumps is not set too high,
– the heating systems have been calibrated.
7.5

Condensate accumulation control

Activate the Limit deviation for OPEN signal function to start up condensate accumulation
plants, in particular to avoid problematic excess temperatures. The controller response to set
point deviations which cause the primary valve to open is attenuated. The controller response
to set point deviations which cause the control valve to close remains unaffected.
Functions
Limit deviation for OPEN signal
WE
Configuration
1
CO1, 2, 3, 4 -> F03 - 1
1.0
Limiting factor / 0.1 to 10.0
0
CO5 -> F16
WE
Parameter level / Range of values
1.2
PA1, 2, 3 / 0.2 to 3.2
0.0 °C
PA1, 2, 3 / –30 to 30 °C
65 °C
PA1, 2, 3 / 5 to 90 °C
65 °C
PA1, 2, 3 / 5 to 90 °C
65 °C
PA4 / 20 to 90 °C
65 °C
PA1, 2, 3 / 5 to 90 °C
WE
Configuration
0
CO1, 2, 3, 4 -> F13 - 1
2 °C
Max. deviation / 2 to 10 °C
System-wide functions
EB 5579 EN
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents