the control system in dynamic processes can be limited with regard to time using the Control
system monitoring function.
While valid Modbus requests are registered, the controller resets the time monitoring. Never-
theless, after 30 minutes have elapsed, all level bits are re-initialized to "autonomous" when
an error has occurred.
!
Warning!
You are required to follow the relevant standards and regulations concerning lightning and
overvoltage protection on installation.
Functions
Modbus
Modbus16-bit addressing
Modem function
Control system monitoring
Parameters*
Station address (ST.-NR)
Baud rate (BAUD)
* –> section 9.3 (Description of communication parameter settings)
9.3

Description of communication parameter settings

Station address (ST.-NR)
This address is used to identify the controller in bus or modem mode. In a system, each con-
troller needs to be assigned a unique address.
Baud rate (BAUD)
In a bus system, baud rate refers to the transfer speed between control system and controller.
In modem mode, baud rate refers to the transfer speed between controller and modem.
The baud rate adjusted at the controller must correspond with the baud rate of the control
system, otherwise no communication can be established.
Cyclical initialization (I)
This parameter defines the period of time for a cyclical issue of the initialization command
"ATZ". The command is not issued during dial-up or when connected. "ATZ" causes the pro-
file 0 to be copied to the active profile, provided the modem parameters have been set and
saved in profile 0 using a suitable terminal program. With CO6 -> F04 - 1, cyclical initial-
ization of the modem is not required.
WE
Configuration
1
CO6 -> F01 - 1
0
CO6 -> F02
0
CO6 -> F03 - 0
0
CO6 -> F07
WE
Parameter level / Range of values
255
PA6 / 1 to 247 with CO6 -> F02 - 1: 1 to 32000
9600
PA6 / 19200, 9600
Communication
121
EB 5579 EN

Hide quick links: