Operation
1.9
Setting room and DHW temperature set points
For the heating circuits, the required room temperatures during the day ( Day set point ) and
during the night ( Night set point ) can be set.
In the DHW circuit, the temperature you wish the DHW to be heated to can be set.
The temperature set points for the different control circuits are set at the rotary switches one
after the other:
Desired temperature set point
Heating circuit 1*: Day set point
Heating circuit 1*: Night set point
Heating circuit 2*: Day set point
Heating circuit 2*: Night set point
DHW heating*: DHW temperature set point
Heating circuit 3*: Day set point
DHW heating*: DHW temperature sustained value
Heating circuit 3*: Night set point
* Refer to page 161 for assignment
Parameters
Day set point
Night set point
DHW temperature set point
Proceed as follows:
Turn appropriate rotary switch to "Set point temperature".
Display shows: temperature
q
Set temperature value.
Return the rotary switch to the required operating mode (left side).
20
EB 5579 EN
WE
Rotary switch / Range of values
20 °C
Top, middle / 0 to 40 °C
15 °C
Top, middle / 0 to 40 °C
55 °C
Bottom / Min. to max. DHW temperature
Switch
Position
Top
Top
Middle
Middle
Bottom
Bottom