System-Wide Functions; Automatic Summer Time/Winter Time Changeover; Frost Protection - Samson TROVIS 5579 Mounting And Operating Instructions

Automation system trovis 5500. heating and district heating controller
Table of Contents

Advertisement

7

System-wide functions

7.1

Automatic summer time/winter time changeover

The clock is automatically adjusted on the last Sunday in March at 2.00h and on the last
Sunday in October at 3.00h.
Functions
Summer time/winter time changeover
7.2

Frost protection

Frost protection measures are taken when the outdoor temperature falls below the Frost pro-
tection limit. The switching differential to cancel the frost protection measures is always 1 °C.
4
Frost protection program I (restricted frost protection): frost protection measures are taken
only when all heating circuits in the system are in stand-by mode. The circulation pumps
are automatically switched on and their flow temperature set points are adjusted to
10 °C. The circulation pump in the DHW circuit is automatically switched on only when
the stand-by mode has been adjusted at the rotary switch in all heating circuits. Never-
theless, the storage tank is always recharged to 10 °C if the storage tank temperature
falls below 5 °C.
4
Frost protection program II: the heating circuit circulation pumps are always switched on
automatically. The flow temperature set points of all heating circuits currently in stand-by
mode are set to +10 °C. In the DHW circuit, the circulation pump is always activated. If
the storage tank temperature falls below +5 °C, the storage tank is recharged to +10 °C.
Functions
Frost protection program I
Frost protection program II
Note: Frost protection operation of a pump, a heating circuit or the DHW circuit is only ac-
tive when the frost protection icon
Fixed set point control without outdoor temperature sensor does not include frost protection
monitoring in stand-by mode.
WE
Configuration
1
CO5 -> F08 - 1
WE
Configuration
CO5 -> F09 - 0
3 °C
Frost protection limit / –15 to 3 °C
CO5 -> F09 - 1
3 °C
Frost protection limit / –15 to 3 °C
is indicated on the display.
System-wide functions
EB 5579 EN
95