4 HUMAN INTERFACES
The following figure shows the vertical arrangement of the faceplate panels for relays ordered with the vertical option.
Figure 4–17: UR-SERIES STANDARD VERTICAL FACEPLATE PANELS
a) ENHANCED FACEPLATE
The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event
cause LEDs, and the next four columns contain the 48 user-programmable LEDs.
The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these
latched conditions can also be reset via the
intended for connection to a portable PC.
The USER keys are used by the breaker control feature.
Figure 4–18: TYPICAL LED INDICATOR PANEL FOR ENHANCED FACEPLATE
The status indicators in the first column are described below.
IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are
OK, and that the device has been programmed.
GE Multilin

SETTINGS
INPUT/OUTPUTS
D30 Line Distance Protection System
4.3 FACEPLATE INTERFACE

4.3.2 LED INDICATORS


menu). The RS232 port is
RESETTING
842811A1.CDR
4
4-15