GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 517

Ur series line distance protection system
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 58)
ADDR
REGISTER NAME
8DC8
...Repeated for Digital Element 45
8DDE
...Repeated for Digital Element 46
8DF4
...Repeated for Digital Element 47
8E0A
...Repeated for Digital Element 48
Trip Bus (Read/Write Setting) (6 modules)
8ED0
Trip Bus 1 Function
8ED1
Trip Bus 1 Block
8ED3
Trip Bus 1 Pickup Delay
8ED4
Trip Bus 1 Reset Delay
8ED5
Trip Bus 1 Input (16 items)
8EF5
Trip Bus 1 Latching
8EF6
Trip Bus 1 Reset
8EF8
Trip Bus 1 Target
8EF9
Trip Bus 1 Events
8EFA
Reserved (8 items)
8F02
...Repeated for Trip Bus 2
8F34
...Repeated for Trip Bus 3
8F66
...Repeated for Trip Bus 4
8F98
...Repeated for Trip Bus 5
8FCA
...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (8 modules)
9000
FlexElement 1 Function
9001
FlexElement 1 Name
9004
FlexElement 1 InputP
9005
FlexElement 1 InputM
9006
FlexElement 1 Compare
9007
FlexElement 1 Input
9008
FlexElement 1 Direction
9009
FlexElement 1 Hysteresis
900A
FlexElement 1 Pickup
900C
FlexElement 1 DeltaT Units
900D
FlexElement 1 DeltaT
900F
FlexElement 1 Pickup Delay
9010
FlexElement 1 Reset Delay
9011
FlexElement 1 Block
9013
FlexElement 1 Target
9014
FlexElement 1 Events
9015
...Repeated for FlexElement 2
902A
...Repeated for FlexElement 3
903F
...Repeated for FlexElement 4
9054
...Repeated for FlexElement 5
9069
...Repeated for FlexElement 6
907E
...Repeated for FlexElement 7
9093
...Repeated for FlexElement 8
Fault Report Settings (Read/Write Setting)
9200
Fault Report 1 Source
9201
Fault Report 1 Trigger
9203
Fault Report 1 Z1 Magnitude
9204
Fault Report 1 Z1 Angle
9205
Fault Report 1 Z0 Magnitude
9206
Fault Report 1 Z0 Angle
9207
Fault Report 1 Line Length Units
9208
Fault Report 1 Line Length
9209
Fault Report 1 VT Substitution
GE Multilin
RANGE
0 to 1
0 to 4294967295
0 to 600
0 to 600
0 to 4294967295
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
---
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
0.1 to 50
-90 to 90
0 to 2
20 to 86400
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 5
0 to 4294967295
0.01 to 250
25 to 90
0.01 to 650
25 to 90
0 to 1
0 to 2000
0 to 2
D30 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F300
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
---
F206
---
1
F600
---
1
F600
---
1
F516
---
1
F515
---
1
F517
%
0.1
F001
pu
0.001
F004
---
1
F518
0 (Milliseconds)
---
1
F003
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F300
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
1
F147
---
0.1
F001
---
1
F270
DEFAULT
0 (Disabled)
0
0
0
0
0 (Disabled)
B
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
"FxE 1"
0
0
0 (LEVEL)
0 (SIGNED)
0 (OVER)
30
1000
20
0
0
0
0 (Self-reset)
0 (Disabled)
0 (SRC 1)
0
300
75
900
75
0 (km)
1000
0 (None)
B-43

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30

Table of Contents