5.6 GROUPED ELEMENTS
b) PHASE UNDERVOLTAGE (ANSI 27P, IEC PTUV)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 UNDERVOLTAGE1
5
This element may be used to give a desired time-delay operating characteristic versus the applied fundamental voltage
(phase-to-ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting
selects the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage
below which the element is blocked (a setting of "0" will allow a dead source to be considered a fault condition).
SETTING
PHASE UV1
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
AND
PHASE UV1
BLOCK:
Off = 0
SETTING
}
PHASE UV1 SOURCE:
Source VT = Delta
VAB
VBC
VCA
Source VT = Wye
SETTING
PHASE UV1 MODE:
Phase to Ground Phase to Phase
VAG
VAB
VBG
VBC
VCG
VCA
5-180
SETTING GROUP 1(6)
PHASE UV1
FUNCTION: Disabled
PHASE UV1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE UV1 MODE:
MESSAGE
Phase to Ground
PHASE UV1
MESSAGE
PICKUP: 1.000 pu
PHASE UV1
MESSAGE
CURVE: Definite Time
PHASE UV1
MESSAGE
DELAY:
PHASE UV1 MINIMUM
MESSAGE
VOLTAGE: 0.100 pu
PHASE UV1 BLOCK:
MESSAGE
Off
PHASE UV1
MESSAGE
TARGET: Self-reset
PHASE UV1
MESSAGE
EVENTS: Disabled
SETTING
PHASE UV1
MINIMUM VOLTAGE:
<
VAG or VAB
Minimum
<
VBG or VBC
Minimum
<
VCG or VCA
Minimum
Figure 5–92: PHASE UNDERVOLTAGE1 SCHEME LOGIC
D30 Line Distance Protection System

VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: Phase to Ground, Phase to Phase
Range: 0.000 to 3.000 pu in steps of 0.001
Range: Definite Time, Inverse Time
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.000 to 3.000 pu in steps of 0.001
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTING
PHASE UV1
PICKUP:
PHASE UV1
CURVE:
PHASE UV1
DELAY:
<
AND
RUN
VAG or VAB PICKUP
t
V
<
AND
RUN
VBG or VBC PICKUP
t
V
<
VCG or VCA PICKUP
AND
RUN
t
V
5 SETTINGS
PHASE UNDERVOLTAGE1(3)
FLEXLOGIC OPERANDS
PHASE UV1 A PKP
PHASE UV1 A DPO
PHASE UV1 A OP
PHASE UV1 B PKP
PHASE UV1 B DPO
PHASE UV1 B OP
PHASE UV1 C PKP
PHASE UV1 C DPO
PHASE UV1 C OP
FLEXLOGIC OPERAND
OR
PHASE UV1 PKP
FLEXLOGIC OPERAND
OR
PHASE UV1 OP
FLEXLOGIC OPERAND
AND
PHASE UV1 DPO
827039AB.CDR