GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 490

Ur series line distance protection system
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 58)
ADDR
REGISTER NAME
26F4
IEC 61850 Received uinteger 3
26F6
IEC 61850 Received uinteger 4
26F8
IEC 61850 Received uinteger 5
26FA
IEC 61850 Received uinteger 6
26FC
IEC 61850 Received uinteger 7
26FE
IEC 61850 Received uinteger 8
2700
IEC 61850 Received uinteger 9
2702
IEC 61850 Received uinteger 10
2704
IEC 61850 Received uinteger 11
2706
IEC 61850 Received uinteger 12
B
2708
IEC 61850 Received uinteger 13
270A
IEC 61850 Received uinteger 14
270C
IEC 61850 Received uinteger 15
270E
IEC 61850 Received uinteger 16
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
Expanded Contact Input/Output States (Read Only)
2D00
Contact Input States, one per register (96 items)
2D80
Contact Output States, one per register (64 items)
2E00
Virtual Output States, one per register (96 items)
Expanded Remote Input/Output Status (Read Only)
2F00
Remote Device States, one per register (32 items)
2F80
Remote Input States, one per register (64 items)
Oscillography Values (Read Only)
3000
Oscillography Number of Triggers
3001
Oscillography Available Records
3002
Oscillography Last Cleared Date
3004
Oscillography Number of Cycles Per Record
Oscillography Commands (Read/Write Command)
3005
Oscillography Force Trigger
3011
Oscillography Clear Data
Oscillography Analog Values (Read Only)
3012
Oscillography Number of Triggers
Fault Report Indexing (Read Only Non-Volatile)
3020
Number of Fault Reports
Fault Report Actuals (Read Only Non-Volatile) (15 modules)
3030
Fault Report 1 Time
3032
Fault Report 2 Time
3034
Fault Report 3 Time
3036
Fault Report 4 Time
3038
Fault Report 5 Time
303A
Fault Report 6 Time
303C
Fault Report 7 Time
303E
Fault Report 8 Time
3040
Fault Report 9 Time
3042
Fault Report 10 Time
3044
Fault Report 11 Time
3046
Fault Report 12 Time
3048
Fault Report 13 Time
304A
Fault Report 14 Time
304C
Fault Report 15 Time
Modbus File Transfer (Read/Write)
3100
Name of file to read
B-16
RANGE
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 400000000
0 to 65535
0 to 1
0 to 1
0 to 32767
0 to 65535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
---
D30 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F108
---
1
F108
---
1
F108
---
1
F108
---
1
F155
---
1
F108
---
1
F001
---
1
F001
---
1
F050
---
1
F001
---
1
F126
---
1
F126
---
1
F001
---
1
F001
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
1
F050
---
---
F204
DEFAULT
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Off)
0 (Off)
0 (Off)
0 (Off)
0 (Offline)
0 (Off)
0
0
0
0
0 (No)
0 (No)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
(none)