GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 171

Ur series line distance protection system
Table of Contents

Advertisement

5 SETTINGS
k) TFTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 TFTP PROTOCOL
MESSAGE
MESSAGE
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the D30 over a network. The D30 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the D30 contains a list and description of all available files (event records, oscillography, etc.).
When the
TFTP MAIN UDP PORT NUMBER
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
NOTE
those protocols.
l) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 60870-5-104
 PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The D30 supports the IEC 60870-5-104 protocol. The D30 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the D30 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the D30 at one time.
GE Multilin


COMMUNICATIONS
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER:
69
TFTP DATA UDP PORT 1
NUMBER:
0
TFTP DATA UDP PORT 2
NUMBER:
0
is set to 0, the change takes effect when the D30 is restarted.


COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
IEC TCP PORT
NUMBER: 2404
 IEC NETWORK
 CLIENT ADDRESSES
IEC COMMON ADDRESS
OF ASDU:
0
IEC CYCLIC DATA
PERIOD:
60 s
IEC CURRENT DEFAULT
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
IEC POWER DEFAULT
THRESHOLD: 30000
IEC ENERGY DEFAULT
THRESHOLD: 30000
IEC PF DEFAULT
THRESHOLD: 1.00
IEC OTHER DEFAULT
THRESHOLD: 30000
IEC REDUNDANCY
ENABLED: No
D30 Line Distance Protection System
5.2 PRODUCT SETUP
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 65535 in steps of 1
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
Range: 1 to 65535 s in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0.00 to 1.00
Range: 0 to 65535 in steps of 1
Range: No, Yes
5
5-45