C.5.1 Overview - GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual

Ur series line distance protection system
Table of Contents

Advertisement

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
C.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
The D30 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1.
An ICD file is generated for the D30 by the EnerVista UR Setup software that describe the capabilities of the IED.
2.
The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3.
The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
C
The following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC
61850:
BDA: Basic Data Attribute, that is not structured
DAI: Instantiated Data Attribute
DO: Data Object type or instance, depending on the context
C-12
Figure C–1: IED CONFIGURATION PROCESS
D30 Line Distance Protection System
APPENDIX C

C.5.1 OVERVIEW

GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30

Table of Contents