Phase Current - GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual

Ur series line distance protection system
Table of Contents

Advertisement

5 SETTINGS
a) MAIN MENU

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE CURRENT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) INVERSE TIME OVERCURRENT CURVE CHARACTERISTICS
The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I
dard curve shapes. This allows for simplified coordination with downstream devices.
If none of these curve shapes is adequate, FlexCurves may be used to customize the inverse time curve characteristics.
The definite time curve is also an option that may be appropriate if only simple protection is required.
Table 5–11: OVERCURRENT CURVE TYPES
IEEE
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (
) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
CURVE
to the time multiplier (
TD MULTIPLIER
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: "Instantaneous" and "Timed". The "Instan-
taneous" selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The "Timed" selection can be used where the relay must
coordinate with electromechanical relays.
IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
GE Multilin
SETTING GROUP 1(6)
 PHASE TOC1
 PHASE TOC2
 PHASE IOC1
 PHASE IOC2
 PHASE IOC3
 PHASE IOC4
 PHASE
 DIRECTIONAL 1
 PHASE
 DIRECTIONAL 2
IEC
IEC Curve A (BS142)
IEC Curve B (BS142)
IEC Curve C (BS142)
IEC Short Inverse
) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
D30 Line Distance Protection System


PHASE CURRENT

See page 5–156.
See page 5–156.
See page 5–158.
See page 5–158.
See page 5–158.
See page 5–158.
See page 5–159.
See page 5–159.
GE TYPE IAC
IAC Extremely Inverse
IAC Very Inverse
IAC Inverse
IAC Short Inverse
5.6 GROUPED ELEMENTS
5.6.7 PHASE CURRENT
2
t stan-
OTHER
2
I
t
FlexCurves A, B, C, and D
Recloser Curves
Definite Time
5-151
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30

Table of Contents