GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 417

Ur series line distance protection system
Table of Contents

Advertisement

8 SECURITY
Timeout
Timeout in seconds between re-
transmission requests
Retries
Number of retries before giving up
Confirm RADIUS
Confirmation of the shared secret. The
Authentication
entry displays as asterisks.
(Shared) Secret
General Security Settings
SETTING NAME
DESCRIPTION
Session Lockout
Number of failed authentications before the
device blocks subsequent authentication
attempts for the lockout period
Session Lockout
The period in minutes that a user is prevented
Period
from logging in after being locked out
Syslog Server IP
The IP address of the target Syslog server to
Address
which all security events are transmitted
Syslog Server Port
The UDP port number of the target syslog server
Number
to which all security events are transmitted
Local Authentication When enabled, local authentication with roles is
allowed. When disabled, the UR only
authenticates to the AAA server (RADIUS).
NOTE: Administrator and Supervisor (if still
enabled) remain active even after local
authentication is disabled. The only permission
for local Administrator is to re-enable local
authentication when local authentication is
disabled. To re-enable local authentication, the
Supervisor unlocks the device for setting
changes, and then the Administrator can re-
enable local authentication.
Firmware Locked
Indicates if the device receives firmware
upgrades. If Yes and the firmware upgrade
attempt is made, the device denies the upgrade
and displays an error message that the lock is
set. On each firmware upgrade, this setting goes
back to the default.
Factory Service
When enabled (checkbox selected), the device
Mode
can go into factory service mode. To enable,
Supervisor authentication is necessary.
Restore to Defaults Sets the device to factory defaults
Supervisor role
When enabled (checkbox selected), the
Supervisor role is active. To enable,
Administrator authentication is necessary. When
disabled, the Supervisor role is inactive. To
disable, Supervisor authentication is necessary.
RADIUS user
Ensure that RADIUS user names are not the
names
same as local role names
Password
Local roles except for Observer are password-
protected. All RADIUS users are password-
protected.
GE Multilin
0
0
See the
following
password
section for
requirements
MIN
0 (lockout
disabled)
0 (no period) 9999
0.0.0.0
1
Disabled
No
Disabled
No
Disabled
See RADIUS
server
documents
See the
following
password
section for
requirements
D30 Line Distance Protection System
8.2 CYBERSENTRY
9999
10
9999
3
245 characters
N/A
MAX
DEFAULT UNITS MINIMUM
99
3
-
3
min
223.255.
0.0.0.0
-
255.254
65535
514
-
Enabled
Enabled
-
Yes
Yes
-
Enabled
Disabled
-
Yes
No
-
Enabled
Enabled
-
See
-
RADIUS
server
documents
See the
Change
Text
following
Me1#
password
section for
requireme
nts
sec
Administrator
-
Administrator
-
Administrator
PERMISSION
Administrator
Administrator
Administrator
Administrator
Administrator
Administrator
Supervisor
(Administrator
when Supervisor
is disabled)
Administrator
Administrator to
enable and
Supervisor to
disable
Administrator
8
The specified role
and Administrator,
except for
Supervisor, where
it is only itself
8-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30

Table of Contents