Signal Communication Error With Transmission Processor - Mitsubishi Electric PUMY-P112VKM3 Technical & Service Manual

City multi series split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM3:
Table of Contents

Advertisement

Check code

Signal communication error with transmission processor

6606
(A6)
Abnormal points and detection methods
Abnormal if the data of unit/transmission processor were not normally
transmitted.
Abnormal if the address transmission from the unit processor was not
normally transmitted.
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Turn the power OFF of indoor/outdoor unit, Fresh
Master, Lossnay and remote controller simultaneously
for 2 minutes or more, then turn the power back ON.
Does it operate normally?
OCH632A
Diagnosis
Yes
Causes and check points
Accidental disturbance such as noise or lightning
surge
Hardware malfunction of transmission processor
Replace the controller.
No
(Defect of error source controller).
There is no abnormality on the AC unit.
It might be caused by an external noise, so check
the transmission line to remove the factor(s).
88