8-8. HOW TO CHECK THE COMPONENTS
<Thermistor feature chart>
Low temperature thermistors
• Thermistor <HIC pipe> (TH2)
• Thermistor <Outdoor liquid pipe> (TH3)
• Thermistor <Suction pipe> (TH6)
• Thermistor <Ambient> (TH7)
Thermistor R0 = 15 k" ± 3 %
B constant = 3480 ± 2 %
1
R
=15exp{3480(
t
273+t
273
0:
15 k"
30:
10:
9.6 k"
40:
20:
6.3 k"
25:
5.2 k"
Medium temperature thermistor
• Thermistor <Heat sink> (TH8)
Thermistor R50 = 17 k" ± 2 %
B constant = 4170 ± 3 %
1
R
=17exp{4170(
t
273+t
0:
180 k"
25:
50 k"
50:
17 k"
70:
8 k"
90:
4 k"
High temperature thermistor
• Thermistor <Compressor> (TH4)
Thermistor R120 = 7.465 k" ± 2 %
B constant = 4057 ± 2 %
1
R
=7.465exp{4057(
t
273+t
20:
250 k"
70:
30:
160 k"
80:
40:
104 k"
90:
50:
70 k"
100:
60:
48 k"
110:
OCH632A
1
)}
4.3 k"
3.0 k"
(Only YKM)
1
)}
323
1
)}
393
34 k"
24 k"
17.5 k"
13.0 k"
9.8 k"
50
40
30
20
10
0
−20 −10 0 10 20 30 40 50
200
150
100
50
0
500
400
300
200
100
0
113
Temperature (:)
25
50
75
100 110 125 :
Temperature
25
50
75
100
120
Temperature (:)