Mitsubishi Electric PUMY-P112VKM3 Technical & Service Manual page 46

City multi series split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM3:
Table of Contents

Advertisement

E. Example of a system using Branch Box and A-Control indoor unit
L
3
L
4
A
L
5
A : Shielded wire
( ): Address example
a. Always use shielded wire when making connections between the outdoor unit (OC) and the Branch Box, as well for
all OC-OC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable terminal block (TB5)
of the Branch Box.
c. Connect terminals 1 and 2 on the transmission cable terminal block (TB5/TB15) of the A-control indoor unit (A-IC), to
the terminal block on the MA remote controller (MA-RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for centralized control (TB7) for the outdoor
unit (OC).
e. DO NOT change the jumper connector CN41 on outdoor multi controller circuit board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit to the earth.
g. Set the address setting switch as follows.
Unit
A-IC
Branch Box
Outdoor Unit
MA Remote Controller
OCH632A
OC
(51)
L
1
TB3
TB7
M1 M2 S M1 M2 S
A
L
2
OC
(53)
TB7
TB3
A
M1 M2
S
M1 M2 S
Power Supply
Unit
M1 M2 S
System
controller
M1 M2 S
Range
According to the set address of connected Branch Box, set the A-IC addresses
sequentially by SW1 on Branch Box.
01 to 50
(For example, when setting the Branch Box address to 01, A-IC addresses set
02,03,04, and 05. )
Use a number within the range 1–50, but it should not make the highest
01 to 50
address of connected A-IC exceed 50.
Use the smallest address of all the Branch Box plus 50.
51 to 100
The address automatically becomes "100" if it is set as "01–50".
-
Address setting is not necessary.
L
6
TB3A
Branch Box
S1
S2
S3
TB5
TB3B
M1
S1
S2
M2
S3
S
TB3C
S1
S2
S3
(01)
TB3D
S1
S2
S3
TB3E
S1
S2
S3
TB3A
Branch Box
S1
S2
S3
TB5
TB3B
(06)
M1
S1
S2
M2
S3
S
TB3C
S1
S2
S3
Setting Method
46
m
1
TB
TB5/TB15
1
A
S1
A-IC
MA-RC
S2
2
B
(01)
S3
TB
TB5/TB15
A
S1
A-IC
1
MA-RC
S2
2
B
(02)
S3
TB
TB5/TB15
A-IC
1
S1
A
MA-RC
2
B
S2
(03)
S3
TB
S1
A-IC
WL-RC
S2
(04)
S3
TB
S1
A-IC
WL-RC
S2
(05)
S3
TB
TB5/TB15
S1
1
A
A-IC
MA-RC
S2
2
B
(06)
S3
TB
S1
A-IC
S2
(07)
WL-RC
S3
TB
S1
A-IC
WL-RC
S2
(08)
S3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents