Figure 13 PUMY-P140VKM3(-BS)
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0
Figure 14 PUMY-P112/125/140VKM3(-BS) <Heating>
PUMY-P112/125/140YKM3(-BS) <Heating>
PUMY-P112/125/140YKME3(-BS) <Heating>
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0
(2) Method for Obtaining the Equivalent Piping Length
Equivalent length for type P112·125·140 = (length of piping to farthest indoor unit) + (0.3 o number of bends in the piping) (m)
Length of piping to farthest indoor unit: type P112–P140.....150 m
4-5-1. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction
factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature (W.B.°C)
Correction factor
OCH632A
PUMY-P140YKM(E)3(-BS) <Cooling>
20
40
60
Piping equivalent length (m)
20
40
60
6
4
2
1.0
0.98
0.89
80
100
120
80
100
120
Piping equivalent length (m)
0
−2
−4
0.88
0.89
0.9
25
Total capacity of indoor unit
7.8
11.6
15.5
20.2
140
160
180
140
160
180
−6
−8
−10
−15
0.95
0.95
0.95
0.95
−20
0.95