Check code
4210
(UP)
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Continued from the previous page
Are they connected properly?
Check the operation of indoor/outdoor fan
motors.
Does it operate normally?
Check for indoor/outdoor short-cycle.
Are those units short-cycled?
Disconnect the compressor wiring from the outdoor
power circuit board, then check the voltage among
each phases U, V and W during test run (SW7-1 ON).
Are the voltage among the phases
U-V, V-W and W-U different?
Replace the outdoor multi controller circuit
board.
Does it operate normally?
OCH632A
Compressor overcurrent interruption
Diagnosis
Yes
Yes
(short-cycled)
(no short-cycled)
No
Yes
Yes
Connect the compressor wiring (U, V and
W phase) properly, then turn the power
No
back ON.
No
Yes
Remove factor(s) causing the short-cycle.
Make sure to perform a voltage
check with the same performing
frequencies.
No
No
Replace the outdoor power circuit board.
Replace the outdoor multi controller circuit
board.
70
Chart 2 of 2
Remedy
Check the DC fan motor.
Replace the compressor.