9-2-2. Cross section area of Wire for Main Power and ON/OFF capacities
PUMY-P112VKM3(-BS)
PUMY-P112YKM3(-BS)
PUMY-P112YKME3(-BS)
<Outdoor unit> <When power is supplied to outdoor unit and branch box separately>
Model
P112–140VKM3
Outdoor Unit
P112–140YKM3
P112–140YKME3
<Outdoor unit> <When power is supplied to branch box from the outdoor unit>
Model
P112–140VKM3
Outdoor Unit
P112–140YKM3
P112–140YKME3
1
*
A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
<Indoor units> <When power is supplied to indoor unit and outdoor unit separately>
Total operating current of the indoor unit
3
F0 = 16 A or less *
3
F0 = 25 A or less *
3
F0 = 32 A or less *
Apply to IEC61000-3-3 about max. permissive system impedance.
2
*
The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
3
*
Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 14)/C}
Connect to Branch box (PAC-MK·BC(B))
Type 1
PEAD-RP·JA(L)Q
Type 2
SEZ-KD·VAQ(L), PCA-RP·KAQ, PLA-ZRP·BA, PLA-RP·EA, SLZ-KF·VA2
Type 3
MLZ-KA·VA
Type 4
MFZ-KJ·VE2
Type 5
MSZ-FH·VE2, MSZ-SF·VE3, MSZ-EF·VE3, MSZ-SF·VA, MSZ-GF·VE
Type 6
Branch box (PAC-MK·BC(B))
Type 7
ecodan C generation
*5 This value may increase due to a locally connected actuator.
Connect to Connection kit (PAC-LV11M-J)
Type 8
MFZ-KJ·VE2
Type 9
MSZ-GE·VA, MSZ-SF·VA, MSZ-SF·VE3, MSZ-EF·VE3, MSZ-FH·VE2
Type 10
Connection kit (PAC-LV11M-J)
Type 11
PEFY-VMA(L)-E, PEFY-VMA3-E
PMFY-VBM-E, PLFY-VBM-E, PLFY-VFM-E1, PEFY-VMS1(L)-E,
Type 12
PCFY-VKM-E, PKFY-VHM-E, PKFY-VKM-E, PFFY-VKM-E2, PFFY-VLRMM-E
Type 13
PKFY-VBM-E
PLFY-VLMD-E, PEFY-VMR-E-L/R, PDFY-VM-E, PEFY-VMH-E, PFFY-VLEM-E,
Type 14
PFFY-VLRM-E, PWFY-VM-E1(2)-AU, PEFY-P·VMH-E-F, GUF-RD(H)4
OCH632A
PUMY-P125VKM3(-BS)
PUMY-P125YKM3(-BS)
PUMY-P125YKME3(-BS)
Minimum Wire Cross-sectional
Power Supply
Main Cable
~/N 220/230/240 V, 50 Hz
~/N 220 V, 60 Hz
3N~380/400/415 V, 50 Hz
3N~380 V, 60 Hz
3N~380/400/415 V, 50 Hz
Minimum Wire Cross-sectional area (mm²)
Power Supply
Main Cable
~/N 220/230/240 V, 50 Hz
~/N 220 V, 60 Hz
3N~380/400/415 V 50 Hz
3N~380 V, 60 Hz
3N~380/400/415 V 50 Hz
Minimum wire thickness (mm²)
Main Cable
Branch
1.5
1.5
2.5
2.5
4.0
4.0
Indoor unit
Indoor unit
Indoor unit
area (mm²)
Breaker for Wiring *
Branch
Ground
6
6
1.5
1.5
Breaker for Wiring *
Branch
Ground
6
6
2.5
2.5
Ground-fault interrupter *
Ground
1.5
20 A current sensitivity *
2.5
30 A current sensitivity *
4.0
40 A current sensitivity *
V1
26.9
19.8
9.9
7.4
6.8
5.1
V1
7.4
6.8
3.5
V1
38.0
19.8
3.5
0.0
134
PUMY-P140VKM3(-BS)
PUMY-P140YKM3(-BS)
PUMY-P140YKME3(-BS)
1
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 seconds or less
16 A
16 A 30 mA 0.1 seconds or less
1
Breaker for Current Leakage
40 A
40 A 30 mA 0.1 seconds or less
20 A
20 A 30 mA 0.1 seconds or less
Local switch (A)
Breaker for wiring
2
Capacity
Fuse
4
16
16
4
25
25
4
32
32
V2
2.4
3.0
*5
5.0
V2
2.4
V2
1.6
2.4
2.4
0.0
Continue to the next page
(NFB)
20
30
40