Address Setting Error; Indoor Unit - Mitsubishi Electric PUMY-P112VKM3 Technical & Service Manual

City multi series split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM3:
Table of Contents

Advertisement

Check code
7105
(EF)
Abnormal points and detection methods
The address setting of connected unit is wrong.
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
<Outdoor unit>
Check whether the outdoor unit address is
set in 000, or in the range of 51 to 100.
Is the address setting correct?
<Indoor unit>
Check whether the indoor unit address is
set in 00, or in the range of 01 to 50.
Is the address setting correct?
<Branch box>
Check whether the branch box address is
set in 00, or in the range of 01 to 46.
Is the address setting correct?
OCH632A

Address setting error

Diagnosis
Yes
Yes
Yes
Causes and check points
There is a unit without correct address setting in the
range specified in "7-5. SYSTEM CONTROL".
Set the address properly, then turn the
power OFF of indoor/outdoor unit, Fresh
Master, Lossnay and remote controller
No
simultaneously for 2 minutes or more, and
turn the power back ON.
Replace the outdoor multi controller circuit
board.
Set the address properly, then turn the
power OFF of indoor/outdoor unit, Fresh
Master, Lossnay and remote controller
No
simultaneously for 2 minutes or more, and
turn the power back ON.
Replace the indoor controller board.
Set the address properly, then turn the
power OFF of indoor/outdoor unit, Fresh
Master, Lossnay and remote controller
No
simultaneously for 2 minutes or more, and
turn the power back ON.
Replace the branch box controller board.
101
Chart 1 of 2
Remedy