Mitsubishi Electric PUMY-P112VKM3 Technical & Service Manual page 56

City multi series split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM3:
Table of Contents

Advertisement

Check code
1302
(UE)
Abnormal points and detection methods
(1) High pressure abnormality (63H operation)
Abnormal if 63H operates(*) during compressor operation. (* 4.15 MPaG
[602 PSIG])
(2) High pressure abnormality (63HS detected)
1. Abnormal if a pressure detected by 63HS is 4.31 MPaG [625 PSIG]
or more during compressor operation.
2. Abnormal if a pressure detected by 63HS is 4.14 MPaG [600 PSIG]
or more for 3 minutes during compressor operation.
63H : High pressure switch
63HS : High pressure sensor
LEV : Electronic expansion valve
SV1 : Solenoid valve
TH7 : Thermistor <Ambient>
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Is 5201 displayed when restarted?
Is the outdoor stop valve (liquid/
gas) fully open?
Does the outdoor fan rotate while
the operation?
Does the indoor fan rotate while
the operation?
Is the indoor unit short-cycled?
Continue to the next page
OCH632A
High pressure trouble
Diagnosis
(5201)
(1302)
No
Yes
Yes
Yes
(short-cycled)
(no short-cycle)
No
Causes and check points
Defective operation of stop valve (not fully open)
Clogged or broken pipe
Malfunction or locked outdoor fan motor
Short-cycle of outdoor unit
Dirt of outdoor heat exchanger
Remote controller transmitting error caused by noise interference
Contact failure of the outdoor multi controller circuit board connector
Defective outdoor multi controller circuit board
Short-cycle of indoor unit
Decreased airflow, clogged filter, or dirt on indoor unit.
Malfunction or locked indoor fan motor
Decreased airflow caused by defective inspection
of outdoor temperature thermistor (It detects lower
temperature than actual temperature.)
Indoor LEV performance failure
Malfunction of fan driving circuit
SV1 performance failure
Defective High pressure sensor
Defective High pressure sensor input circuit on
outdoor multi controller circuit board
Refer to the diagnosis of check code 5201.
Yes
Open the stop valve (liquid/gas) fully.
No
Check the outdoor fan motor.
Refer to "How to check the parts" on the
No
outdoor unit service manual.
Check the indoor fan motor.
No
Refer to "How to check the parts" on the
indoor unit service manual.
Yes
56
Chart 1 of 4
Remedy
Solve the short-cycle.