Unit Specifications - Mitsubishi Electric PUMY-P112VKM3 Technical & Service Manual

City multi series split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM3:
Table of Contents

Advertisement

2-4. UNIT SPECIFICATIONS

(1) Outdoor Unit
Service Ref.
Cooling (kW)
Capacity
Heating (kW)
Compressor (kW)
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
*Cooling
Indoor
: D.B. 27°C/W.B. 19.0°C
Outdoor : D.B. 35°C
Heating
Indoor
: D.B. 20°C
Outdoor : D.B. 7°C/W.B. 6°C
(2) Method for identifying MULTI-S model
Outdoor unit <When using model 125 >
PU M Y - P 125 Y K M E 3 - BS
Refrigerant
Outdoor unit
R410A
MULTI-S
Frequency
conversion
controller
Indicates equivalent
to Cooling capacity
(kcal/ h)
(3) Operating temperature range
Indoor-side intake air temperature
Outdoor-side intake air temperature
Notes:
D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*
1
10 to 52°C D.B. : When connecting PKFY-P15/P20/P25VBM, PFFY-P20/25/32VKM, PFFY-P20/25/32VLE(R)M, PEFY-P25/32/40VMA3-E;
and M series, S series, and P series type indoor unit.
When connecting fresh air type indoor unit
Indoor-side and Outdoor-side
intake air temperature
*
2
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 21 : D.B..
*
3
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 20 : D.B..
When connecting PWFY unit
Indoor-side intake water temperature
Outdoor-side intake air temperature
*
4
• PWFY series can operate in Heating mode but not in Cooling mode. An indoor unit other than that of PWFY series can
operate in Cooling mode.
• A PWFY series and other series cannot operate simultaneously.
• The operation of PWFY series takes precedence over other series. While a PWFY series is operating, other series do not operate.
• The set temperature on the remote controller represents the target temperature of the outlet water.
OCH632A
PUMY-P112VKM3(-BS)
PUMY-P112YKM(E)3(-BS)
12.5
14.0
2.9
Electrical
box
sub
number
M-NET
Salt proof
type
control
Outdoor unit
model type
Power supply
V: Single phase
220/230/240 V, 50 Hz
Y: 3-phase
380/400/415 V, 50 Hz
380 V, 60 Hz (YKM3 only)
Cooling
W.B. 15 to 24°C
D.B. −5 to 52°C *
1
Capacity of Fresh
Cooling
air type indoor
D.B. 21 to 43: *
P80
W.B. 15.5 to 35:
D.B. 21 to 43: *
P140
W.B. 15.5 to 35:
Cooling
PUMY-P125VKM3(-BS)
PUMY-P125YKM(E)3(-BS)
14.0
16.0
3.5
Heating
D.B. 15 to 27°C
W.B. −20 to 15°C
2
2
*
4
*
4
8
PUMY-P140VKM3(-BS)
PUMY-P140YKM(E)3(-BS)
15.5
18.0
3.9
Heating
D.B.−10 to 20: *
3
D.B. −5 to 20: *
3
Heating
D.B. 10 to 45:
W.B. −20 to 15: