Mitsubishi Electric PUMY-P112VKM3 Technical & Service Manual page 12

City multi series split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM3:
Table of Contents

Advertisement

Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor temp.
cooling
Outdoor temp.
Heating capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor temp.
heating
Outdoor temp.
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level
(measured in anechoic room)
Power pressure level
(measured in anechoic room)
Refrigerant
Liquid pipe
piping diameter
Gas pipe
FAN *2
Type × Quantity
Air flow rate
Control, Driving mechanism
Motor output
External static press.
Compressor
Type × Quantity
Manufacture
Starting method
Capacity control %
Motor output
Case heater
Lubricant
External finish
External dimension HxWxD
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type × original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
*
Nominal cooling conditions
1
Indoor :
27°C D.B./19°C W.B. [81°F D.B/66°F W.B.]
Outdoor :
35°C D.B. [95°F D.B.]
Pipe length :
7.5 m [24-9/16 ft]
Level difference :
0 m [0 ft]
*3 10 to 52:D.B. [50 to 126_F D.B.], when connecting following models: PKFY-P15/20/25VBM, PFFY-P20/25/32VLE(R)M, PFFY-
P20/25/32VKM, PEFY-P25/32/40VMA3; and M series, S series, and P series type indoor unit.
*4 −15 to 52:D.B. [50 to 126_F D.B.], when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not
apply to the indoor unit listed in *3.
*5 Up to P100 when connecting via branch box.
*6 Up to 11 units when connecting via 2 branch boxes.
Notes : 1. Nominal conditions *
, *
1
2. Due to continuing improvement, above specifications may be subject to change without notice.
OCH632A
PUMY-P112YKME3(-BS)
1
kW*
12.5
1
kcal/h*
10,750
1
BTU/h*
42,650
kW
2.79
A
4.46/4.24/4.09
kW/kW
4.48
W.B.
D.B.
2
kW*
14.0
2
kcal/h*
12,040
2
BTU/h*
47,768
kW
3.04
A
4.86/4.62/4.45
kW/kW
4.61
D.B.
W.B.
Citymulti
15 - 140/9
Branch box
15 - 100/8
Mixed system
15 - 140*
dB <A>
49/51
dB <A>
69/71
mm (inch)
mm (inch)
K/min
L/s
cfm
kW
Cooling 26 to 100
Heating 20 to 100
kW
kW
mm
inch
kg (lb)
Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E, Branch box: PAC-MK31/32/51/52BC(B)
*
Nominal heating conditions
2
20°C D.B. [68°F D.B.]
7°C DB/6°C W.B. [45°F D.B./43°F W.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
are subject to ISO 15042.
2
PUMY-P125YKME3(-BS)
3-phase 380/400/415 V, 50 Hz
5.53/5.26/5.07
15 to 24°C
−5 to 52°C
5.98/5.68/5.48
15 to 27°C
−20 to 15°C
50 to 130% of outdoor unit capacity
5
/10
15 - 140*
9.52 (3/8)
15.88 (5/8)
Propeller Fan × 2
DC control
0.06+0.06
Scroll hermetic compressor × 1
Mitsubishi Electric Corporation
Cooling 24 to 100
Heating 18 to 100
2.9
FV50S(2.3litter)
Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
1,338 × 1,050 × 330(+25)
52-11/16 × 41-11/32 × 13 (+1)
High pressure Switch
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor thermistor, Over current detection
Overheating, Voltage protection
R410A 4.8kg
Electronic expansion valve
136 (300)
Cross Fin and Copper tube
HIC circuit
Reversed refrigerant circuit
BK01N339
BH78J358
Installation Manual
Grounded lead wire x2
12
PUMY-P140YKME3(-BS)
14.0
12,040
47,768
3.46
4.05
*3, *4
16.0
13,760
54,592
3.74
4.28
15 - 140/10
15 - 100/8
5
6
/10*
50/52
70/72
110
1,833
3,884
0
Inverter
Cooling 21 to 100
Heating 17 to 100
3.5
0
15.5
13,330
52,886
4.52
7.23/6.87/6.62
3.43
18.0
15,480
61,416
4.47
7.15/6.79/6.55
4.03
15 - 140/12
15 - 100/ 8
5
6
15 - 140*
/10*
51/ 53
71/73
3.9
Unit converter
kcal/h = kW × 860
BTU/h = kW × 3,412
cfm = m³/min × 35.31
lb = kg/0.4536
Above specification data is
subject to rounding
variation.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents