7-5. SYSTEM CONTROL

7-5-1. Example for the System
• Example for wiring control cables, wiring method and address setting, permissible lengths, and the prohibited items are listed
in the standard system with detailed explanation.
A. Example of a M-NET remote controller system (address setting is necessary.)
Example of wiring control cables
1. Standard operation
L
1
OC
(51)
TB3
TB7
M1 M2
S
M1 M2 S
• 1 M-NET remote controller for
each M-NET control indoor unit.
• There is no need for setting
the 100 position on the M-NET
remote controller.
2. Operation using 2 M-NET remote controllers
OC
(51)
TB3
TB7
M1 M2 S
M1 M2 S
• Using 2 M-NET remote
controllers for each M-NET
control indoor unit.
3. Group operation
Group A
OC
(51)
TB3
TB7
M1 M2 S
M1 M2 S
• Multiple M-NET control indoor
units operated together by 1
M-NET remote controller
Combinations of 1 through 3 above are possible.
OCH632A
L
2
M-IC
(01)
TB5
TB15
1 2
M1 M2 S
M1 M2 S
A B
(101)
(102)
M-NET RC
M-NET RC
M-IC
(01)
TB5
TB15
1 2
M1 M2 S
A B
A B
A B
(101)
(151)
(102)
M-NET RC
M-NET RC
M-NET RC
(Main)
(Sub)
(Main)
M-IC(Main)
M-IC(Sub)
(01)
(02)
TB5
TB15
TB5
TB15
1 2
M1 M2 S
M1 M2 S
A B
(101)
M-NET RC
Wiring Method and Address Setting
a. Use feed wiring to connect terminals M1 and M2 on
transmission cable block (TB3) for the outdoor unit
(OC) to terminals M1 and M2 on the transmission
M-IC
cable block (TB5) of each M-NET control indoor unit
(M-IC). Use non-polarized 2-core wire.
(02)
b. Connect terminals M1 and M2 on transmission cable
TB5
TB15
terminal block (TB5) for each indoor unit with the termi-
1 2
nal block (TB6) for M-NET the remote controller (M-NET
RC).
c. Set the address setting switch (on outdoor unit P.C.B)
as shown below.
Unit
A B
M-NET control
indoor unit (M-IC) 001 to 050
Outdoor unit (OC) 051 to 100
M-NET Remote
controller (M-NET RC)
a. Same as above a
b. Same as above b
c. Set address switch (on outdoor unit P.C.B) as
M-IC
shown below.
(02)
Unit
TB5
TB15
M-NET control
1 2
M1 M2 S
indoor unit (M-IC)
Outdoor unit (OC) 051 to 100
Main M-NET
Remote Controller
A B
(M-NET RC)
Sub M-NET
(152)
Remote Controller
M-NET RC
(M-NET RC)
(Sub)
a. Same as above a
b. Connect terminals M1 and M2 on transmission cable termi-
nal block (TB5) of the M-IC main unit with the most recent
address within the same M-NET control indoor unit (M-IC)
group to terminal block (TB6) on the M-NET remote controller.
c. Set the address setting switch (on outdoor unit P.C.B) as
shown below.
Unit
M-IC (Main)
1 2
M-IC (Sub)
Outdoor unit
Main M-NET
Remote Controller
(M-NET RC)
d. Use the M-NET control indoor unit (M-IC) within the
group with the most functions as the M-IC (Main) unit.
38
Range
Setting Method
Use the smallest address of all
the indoor unit plus 50.
101 to 150 Indoor unit address plus 100
Range
Setting Method
001 to 050
Use the smallest address of all
the indoor units plus 50.
101 to 150 Indoor unit address plus 100
151 to 200 Indoor unit address plus 150
Range
Setting Method
Use the smallest address within
001 to 050
the same group of M-NET control
indoor units.
Use an address, other than that of
the M-IC (Main) from among the units
001 to 050
within the same group of indoor units.
This must be in sequence with the
M-IC (Main).
Use the smallest address of all the
051 to 100
M-NET control indoor units plus 50.
Set at an M-IC (Main) address
101 to 150
within the same group plus 100.