1-3. Unit Specifications

(1) Outdoor Unit
Model name
Capacity
Power source
Power input
Current
Type
Quantity
Fan
Airflow rate
Motor output
Type
Compressor
Motor output
Crankcase heater
Heat exchanger
Refrigerant / Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Compressor
Fan
Inverter
Refrigerant
High press. pipe
piping diameter
Low press. pipe
Noise level
Net weight
Note: *1. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
<Cooling>
<Heating>
*2. It is measured in anechoic room.
**
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
(2) Indoor Unit
Model name
System capacity
Power source
Power input
Current
Type x Quantity
Airflow rate
Fan
External static pressure
Motor Output
Refrigerant
External finish
External dimensions H x W x D
Protection devices (Fan)
Single refrigerant
Refrigerant
circuit
piping diameter
Two refrigerant
2
circuit
Refrigerant piping allowable length
Noise level
Heat exchanger
Air filter
Net weight
Note: *1. Heating can be used only by the indoor warming-up.
*2. At factory shipment, this model of indoor unit is designed and set to accommodate a single refrigerant circuit.
Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work.
**
Installation/foundation work, electric connection work, duct work, insulation work, power source switch and other items are
not specified in the specifications.
PUHY-P250YGM-A (-BS)
connected with PFD series
Cooling
kW
28.0
1
kW
6.8
A
11.4/10.9/10.5
Propeller fan x 1
m
3
/min
kW
kW
kW
Pre-coated galvanized sheets (+ powder coating for -BS type) <MUNSEL 5Y 8/1 or similar>
1,840 x 990 x 840
mm
ø9.52 Flare (ø12.7 for over 90m)
2
dB(A)
kg
Indoor : 27˚CDB / 19˚CWB
Indoor : 20˚CDB
Pipe length : 7.5m
PFD-P250VM-E
Cooling
kW
28.0
kW
A
Sirocco fan x 1
m
3
/min
Pa
kW
mm
1,950 x 1,380 x 780
Liquid pipe
ø 9.52 Brazed (ø 12.7 for over 90m)
Gas pipe
m
dB(A)
kg
Heating
31.5
3N ~ 380/400/415V 50/60Hz
6.6
11.1/10.5/10.2
200
0.38
Hermetic
6.7
0.045 x 1
Salt resistant fin
R410A/MEL32
4.15MPa
Over current protection / Over heat protection
Thermal switch
Over current protection / Thermal protection
ø22.2 Brazed
57/57
233
Outdoor :
35˚CDB
7˚CDB / 6˚CWB
Outdoor :
Height difference : 0m
Heating
1
31.5
3N~380/400/415V(50Hz), 400/415V(60Hz)
2.5
5.3/5.0/4.9
160
120
2.2
R410A
Galvanized steel plate (with polyester coating)
<MUNSEL 2.9GY 8.6/0.3(White) 7.2GB 3.2/5.3(Blue) or similar>
Thermal switch
ø 22.2 Brazed
-
150
59
Cross fin (Aluminum plate fin and copper tube)
PP Honeycomb fabric (washable)
380
3
PUHY-P500YGM-A (-BS)
connected with PFD series
Cooling
56.0
13.6
22.8/21.8/21.0
22.2/21.0/20.4
Propeller fan x 2
400
0.38 x 2
8.2+5.3
0.045 x 2
1,840 x 1,990 x 840
ø15.88 Flare
ø28.58 Brazed
60/61
455
PFD-P500VM-E
Cooling
56.0
5.0
9.5/9.0/8.7
Sirocco fan x 2
320
120
4.4
1,950 x 1,980 x 780
Liquid pipe
ø 15.88 Brazed
Gas pipe
ø 28.58 Brazed
Liquid pipe ø 9.52 Brazed (ø 12.7 for over 90m)
Gas pipe
ø 22.2 Brazed
150
63
520
Heating
63.0
13.2
Heating
1
63.0