Address Setting The Control Board - Directly From The Board; Address Setting The Control Board - From The User Terminal - Mitsubishi Electric s-MEXT-G00 006-044 Operation Manual

Computer room air conditioner
Table of Contents

Advertisement

UM_s-MEXT_ME28relC_00_12_19_ML
5.2.3.

Address setting the control board - Directly from the board

The control board address is displayed by 7-segment screen in the following image:
In order to display the current address, press the button on the left of the display briefly (for no more than 2 seconds) using, for instance, the tip of a
screwdriver (Ø < 3mm). After 5 seconds from releasing the button, the address display turns off.
In order to change the board address, follow the process below:
1.
Press the button with a screwdriver for at least 3 seconds. The saved address starts flashing.
2.
Press the button repeatedly, or press and hold it to scroll through automatically, to find the required address.
3.
Wait for at least 10 seconds. The display starts flashing quickly to indicate that the new address has been saved.
In order to cancel the operation, turn off the control within 7 seconds of pressing the button last.
4.
Turn off and restart the EVOLUTION+ controller in order to activate the new address.
5.2.4.

Address setting the control board - from the user terminal

1)
Press and hold [UP]+[DOWN]+[ENTER] at the same time for at least 3 seconds to enter configuration mode.
A mask is displayed with the cursor flashing in the top left corner.
2)
Press [ENTER] once to modify the address of the terminal (display address setting). The cursor will move on
the address field.
Press [UP] or [DOWN] to select the value 0 and then press [ENTER] again to confirm. The value will be
saved in the permanent memory of the terminal.
3)
The appearance of the next mask indicates that the keyboard address has been set.
4)
Turn the board off and then on again by pressing and holding [ALARM]+[UP] at the same time. Wait until the
board address setting mask appears, then release the keys.
The mask appears for setting the required address.
ATTENTION
This is a time procedure; hence if the parameters are not set in a few seconds, the display turns off. In such case, repeat the
process.
USER MANUAL
7 segment display for the addressing
procedure using the hardware
Figure 5-2: Control board addressing
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
48
Display address
Setting..........: 21
I/O Board address: 01
Display address
Setting..........: 00
I/O Board address: --
Display address
Changed
#################
selftest
pleasewait...
#################