Enclosure

Enclosure Layout
Please observe the clearances in the diagram below taking into account any appropriate notes for
other devices / auxiliary equipment when planning the installation.
Figure 3-7 Enclosure layout (size 3 to 8)
Locate as
Locate as
required
required
AC supply
contactor and
fuses or MCB
Ensure minimum clearances
are maintained for the drive
and external EMC filter. Forced
or convection air-flow must not
be restricted by any object or
cabling
The external EMC filter can be
bookcase mounted (next to the
drive) or footprint mounted (with
the drive mounted onto the filter).
External
controller
Signal cables
Plan for all signal cables
to be routed at least
300 mm (12 in) from the
drive and any power cable
26
Enclosure
³100mm
(4in)
A
A
Size 3: 0mm (0 in)
Size 4 to 8 ³30mm (1.18 in)
A
Note
For EMC compliance:
1) When using an external EMC
filter, one filter is required for
each drive
2) Power cabling must be at
least 100 mm (4 in) from the
³100 mm
drive in all directions
(4 in)
Powerdrive F300 Getting Started Guide