Ground Connections - Emerson Powerdrive F300 Getting Started Manual

Frame sizes 3 to 11
Hide thumbs Also See for Powerdrive F300:
Table of Contents

Advertisement

A separate line reactor (INLXXX) must be used for size 9E,10E and 11E. Failure to
provide sufficient reactance could damage or reduce the service life of the drive. Refer to
Table 2-8 Size 9E, 10E and 11E Model and Line reactor part number on page 13.
CAUTION
4.4

Ground connections

Electrochemical corrosion of grounding terminals
Ensure that grounding terminals are protected against corrosion i.e. as could be caused
by condensation.
WARNING
The drive must be connected to the system ground of the AC supply. The ground wiring must
conform to local regulations and codes of practice.
For further information on ground cable sizes, refer to Table 2-6 Protective ground cable
NOTE
ratings on page 12.
On size 3 and 4, the supply and motor ground connections are made using the M4 studs located
either side of the drive near the plug-in power connectors. See Figure 4-1 and Figure 4-2 for details.
On size 5, the supply and motor ground connections are made using the M5 studs located near the
plug-in power connector. Refer to Figure 4-3.
On a size 6, the supply and motor ground connections are made using the M6 studs located above
the supply and motor terminals. Refer to Figure 4-4.
On size 7, the supply and motor ground connections are made using the M8 studs located by the
supply and motor connection terminals. Refer to Figure 4-5.
On size 8, the supply and motor ground connections are made using the M10 studs located by the
supply and motor connection terminals. Refer to Figure 4-5.
On size 9A, the supply and motor ground connections are made using the M10 studs located by the
supply and motor connection terminals. Refer to Figure 4-7
On size 9E and 10E, the supply and motor ground connections are made using the M10 studs
located by the supply and motor connection terminals. Refer to Figure 4-7.
On size 11E, the supply and motor ground connections are made using the M10 studs located by the
supply and motor connection terminals. Refer to Figure 4-8.
The ground loop impedance must conform to the requirements of local safety regulations.
The drive must be grounded by a connection capable of carrying the prospective fault
current until the protective device (fuse, etc.) disconnects the AC supply.
WARNING
The ground connections must be inspected and tested at appropriate intervals.
Powerdrive F300 Getting Started Guide