7.2

Quick Start / start-up

7.2.1
Open loop
Action
Ensure:
Before
The drive enable signal is not given (terminal 29)
power-up
Run signal is not given
Motor is connected
Verify that Open Loop mode is displayed as the drive powers
up. If the mode is incorrect see section 5.6
Power-up the
drive
operating mode
Ensure that the drive displays 'Inhibit'
Enter:
Motor rated frequency in Pr 00.047 (Hz)
Enter motor
Motor rated current in Pr 00.046 (A)
nameplate
Motor rated speed in Pr 00.045 (rpm)
details
Motor rated voltage in Pr 00.044 (V) - check if
connection
Set maximum
Enter:
frequency
Maximum frequency in Pr 00.002 (Hz)
Set
Enter:
acceleration /
Acceleration rate in Pr 00.003 (s to Pr 1.006)
deceleration
Deceleration rate in Pr 00.004 (s to Pr 1.006)
rates
Motor
The motor thermistor can be selected in Pr 07.011. Refer to
thermistor
Pr 07.011 for further information.
set-up
Powerdrive F300 Getting Started Guide
Issue Number: 5
on page 52.
Detail
Changing the
or
Mot X XXXXXXXXX
No XXXXXXXXXX kg
°
IP55
I.cl F
C 40 s S1
V
Hz min
-1
kW
cosφ
A
230
50 1445 2.20 0.80 8.50
400
4.90
CN = 14.5Nm
240
50 1445 2.20 0.76 8.50
415
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
0.02
t
100Hz
t
0.03
0.04
67