7.2
Quick Start / start-up
7.2.1
Open loop
Action
Ensure:
Before
•
The drive enable signal is not given (terminal 29)
power-up
•
Run signal is not given
•
Motor is connected
Verify that Open Loop mode is displayed as the drive powers
up. If the mode is incorrect see section 5.6
Power-up the
drive
operating mode
Ensure that the drive displays 'Inhibit'
Enter:
•
Motor rated frequency in Pr 00.047 (Hz)
Enter motor
•
Motor rated current in Pr 00.046 (A)
nameplate
•
Motor rated speed in Pr 00.045 (rpm)
details
•
Motor rated voltage in Pr 00.044 (V) - check if
connection
Set maximum
Enter:
frequency
•
Maximum frequency in Pr 00.002 (Hz)
Set
Enter:
acceleration /
•
Acceleration rate in Pr 00.003 (s to Pr 1.006)
deceleration
•
Deceleration rate in Pr 00.004 (s to Pr 1.006)
rates
Motor
The motor thermistor can be selected in Pr 07.011. Refer to
thermistor
Pr 07.011 for further information.
set-up
Powerdrive F300 Getting Started Guide
Issue Number: 5
on page 52.