APEX
and APEX Sentry
Strapping Table
Figure 3-12. Strapping Table
Example
3-22
™
Radar Gauge
Right click on the device and select "Configuration Properties" from the menu.
Locate the Strapping Table tab and perform the following procedure:
First tell the gauge how many entries you will have; the more entries you
have, the better the gauge will be able to calculate the volume. The maximum
number of strapping points you can enter is 10.
Next, input the actual level and volume points, starting at the bottom of the
tank. It may be desirable to use most of the points in the areas of the tank that
are the least "straight." Suggestion: Set first entry at zero level and zero
volume to enable the gauge to track volume over the entire range.
Reference Manual
00809-0100-4731, Rev FA
April 2003