using supplied tool.
3. Powder Cap loose. Turn Main Power switch to the OFF
(O) position. Tighten Powder Cap to powder bowl
and turn System ON. If cap does not fit tightly, check
for thread wear and replace cap, o-ring seal, or bowl
assembly.
4. Clogged fitting assembly on powder bowl. Refer to
Section 10.5 Powder Bowl Maintenance.
5.
Dental office air source should be serviced to eliminate
the source of the contamination.
Symptom:
System operates: Continuous powder agitation
1. Powder Cap not securely sealed. Turn Main Power
switch to the OFF (O) position and remove Powder Cap.
2. Remove the o-ring seal from the Powder Cap and clean
residual powder from the cap. Be careful not to
scratch or otherwise damage the plastic cap.
3. Wipe off the o-ring and place it in the Powder Cap.
Tighten Powder Cap to Powder Bowl and turn system
ON. Worn caps and o-rings should be replaced when
wear is noted.
11.2 Technical Support and Repairs
For technical support and repair assistance call DENTSPLY
Professional Cavitron Care
1-800-989-8826 Monday through Friday, 8:00 A.M. to 5:00
P.M. (Eastern Time). For areas outside the U.S., contact your
local DENTSPLY Professional representative.
SECTION 12:
Warranty Period
The Cavitron
Prophy-Jet
®
®
for TWO YEARS from date of purchase. The JET-Mate
Handpiece enclosed with your system is warranted for SIX
MONTHS from date of purchase. Refer to the Warranty
Statement Sheet furnished with your system for full Warranty
Statement and Terms.
Factory Certified Service at
SM
Air Polishing System is warranted
SECTION 13:

Specifications

Electrical Voltage
Current
Phase
Frequency
Water Pressure
Water Temperature
Air Pressure
Water Flow Rate
Weight
Dimensions
Footswitch
Remote Communication
Operating Environment
Transport and Storage Conditions Temperature: -40 to 70 Deg.
21
Continuous (100-240 VAC)
1.0 Amperes, Maximum
Single
50/60 Hertz
20 to 40 psig
(138 to 275 kPa)
o
o
< 25
C (77
F)
65 to 100 psig
(448 to 600 kPa)
Minimum Setting
(CCW) < 15 ml/min
Maximum Setting
(CW) > 55 ml/min
4.4 lbs (2 Kg)
Height: 6 in. (15,24 cm)
Width: 9.5 in. (24,13 cm)
Depth: 8 in. (20,32 cm)
Handpiece Cable length:
6.5 ft. (2.0 M)
Auxillary Footswitch Cable
length: 8 ft. (2.4 M)
Water Supply Line length:
8 ft. (2.4 M)
Air Supply Line length:
10 ft. (3.04 M)
Protection Class IPX1. Not
for operating theatres.
Frequency: 2405 to 2480 MHz
Power: < 1mW
Channels:
16
Temperature: 15 to 40 Deg.
Celsius (59 to 104 Deg.Fahrenheit)
Relative Humidity: 30% to 75%
(non-condensing)
Celsius (-40 to 158 Deg.
Fahrenheit)
Relative Humidity: 10% to
100% (non-condensing)
Atmospheric Pressure: 500 to
1060 hPa