Hitachi P1-00080-L Basic Manual page 87

Sj series
Hide thumbs Also See for P1-00080-L:
Table of Contents

Advertisement

Chapter 4
[Cb-01]~ [Cb-35]
Analogue input acquisition
Code/Name
Cb-01
Time constant of filter
Cb-03
Start value
Cb-04
End value
Cb-05
Start rate
Cb-06
End rate
Cb-07
Start selection
Cb-11
Time constant of filter
Cb-13
Start value
Cb-14
End value
Cb-15
Start rate
Cb-16
End rate
Cb-17
Start selection
Cb-21
Time constant of filter
Cb-22
Operation selection
Cb-23
Start value
Cb-24
End value
Cb-25
Start rate
Cb-26
End rate
・Regarding the adjustment method of the Analogue input,
please refer to the chapter 3 example of I/O terminals
adjustment.
Analogue input fine tuning
Code/Name
Cb-30
[Ai1] Voltage/Current zero-bias
adjustment
Cb-31
[Ai1] Voltage/Current gain
adjustment
Cb-32
[Ai2] Voltage/Current
zero-bias adjustment
Cb-33
[Ai2] Voltage/Current gain
adjustment
Cb-34
[Ai3] Voltage -10 bias
adjustment
Cb-35
[Ai3] Voltage gain adjustment
・Regarding the adjustment method of the Analogue input,
please refer to the chapter 3 example of I/O terminals
adjustment.
・The thermistor adjustment, when recognizes an increase
in the adjustment value, reduces the resistor value.
Initial
Range (unit)
value
1~500(ms)
16
0.00~100.00(%)
0.00
0.00~100.00(%)
100.00
0.0~[Cb-06](%)
0.0
100.0
[Cb-05]~100.0(%)
00(Initial value)/
01
01(0%)
1~500(ms)
16
0.00~100.00(%)
0.00
0.00~100.00(%)
100.00
0.0
0.0~[Cb-16](%)
[Cb-15]~100.0(%)
100.0
00(Initial value)/
01
01(0%)
16
1~500(ms)
00(Individual)/
01(Ai1/Ai2 add:
with inversion/
00
02(Ai1/Ai2 add:
without inversion)
-100.00~100.00(%)
-100.00
-100.00~100.00(%)
100.00
-100.0~[Cb-26]
-100.0
100.0
[Cb-25]~100.0
Initial
Range (unit)
value
-200.00
0.00
200.00(%)
-200.00
100.00
200.00(%)
-200.00
0.00
200.00(%)
-200.00
100.00
200.00(%)
-200.00
0.00
200.00(%)
-200.00
100.00
200.00(%)
4-39
For parameter configuration
[CA-40][Cb-41][CC-01]~[CC-17]
Thermistor error detection
Code/Name
CA-40
Thermistor type
selection
Cb-41
Thermistor gain adjustment
・With [CA-40] is set the thermistor connected to the TH terminal.
・When [CA-40]=01 or 02, with [bb-70] the error level is set. Refer to
[bb-70].
・[Cb-41] thermistor gain adjustment, when the adjustment value is
raised the resistance value is lowered.
Output terminal settings
Code/Name
CC-01
Output terminal [11]
CC-02
Output terminal [12]
CC-03
Output terminal [13]
CC-04
Output terminal [14]
CC-05
Output terminal [15]
CC-06
Output terminal [16]
CC-07
Output terminal [AL]
・The functions for the output terminals 11~15,16A,AL are
assigned in [CC-01]~[CC-05],[CC-06],[CC-07].
Output terminal NO/NC settings
Code/Name
CC-11
Output terminal [11] active state
CC-12
Output terminal [12] active state
CC-13
Output terminal [13] active state
CC-14
Output terminal [14] active state
CC-15
Output terminal [15] active state
CC-16
Output terminal [16] active state
CC-17
Output terminal [AL] active state
・The functions for the Intelligent output terminals 11~
15,16,AL are assigned in [CC-11]~[CC-15], [CC-16],
[CC-17].
Initial
Range (unit)
value
00(Disable)/
00
01(PTC)/02(NTC)
0.0~1000.0
100.0
Initial
Range (unit)
value
002
001
035
Reference
<Intelligent
019
output terminal
function list>
030
018
017
Range
Initial
(unit)
value
00
00
00
00(Normally
open: NO)/
00
01(Normally
closed: NC)
00
00
01