Chapter 4
[AJ-13]~[AJ-19]
Code/Name
AJ-13
PID2 proportional gain
AJ-14
PID2 integral time constant
AJ-15
PID2 derivative gain
・Sets the PID2 gain.
・If [PIDC] terminal is active (ON), the value of the
integral constant is purged. If done while operating, the
operation can become instable/insecure.
Code/Name
AJ-16
PID2 output range
PID output (%)
PID
Target
value
・Limits the output range of the PID. If [AJ-16]=0.00 the
limit is disabled.
Code/Name
AJ-17
PID2 deviation level
PID deviation (%)
0%
Output
terminal
ON
047[OD2]
・When the PID deviation pass over ±[AJ-17], the output
terminal function 047[OD2] is activated.
Code/Name
AJ-18
Maximum PID2 feedback
AJ-19
Minimum PID2 feedback
PID feedback (%)
0%
Operation
command
048[FBV2]
ON
・When the PID feedback cross over the [AJ-18] level, the
output terminal function 048[FBV2] is deactivated
(OFF). If it crosses under the [AJ-19] level, is activated
(ON).
Initial
Range (unit)
value
1.0
0.0~100.0
0.0~3600.0(s)
1.0
0.0
0.0~100.0(s)
Range (unit)
Initial value
0.00
0.00~100.00(%)
PID output range
[AJ-16]
[AJ-16
]
Time(s)
Range (unit)
Initial value
0.00~100.00(%)
3.00
[AJ-17]
[AJ-17]
ON
Time(s)
Range (unit)
Initial
value
100.00
0.00~100.00(%)
0.00~100.00(%)
0.00
[AJ-18]
[AJ-19]
Time(s)
ON
ON
For parameter configuration
PID3 function
Code/Name
AJ-21
PID3
enable
・Validates the PID3 operation.
・If [AJ-21]=01 when the PID output reaches a negative
value, the PID output is limited to 0.
・If [AJ-21]=02 when the PID output reaches a negative
value, the PID output lets out an inverted output.
・By activating the [PID3] terminal, the PID3 output
becomes 0.
Code/Name
AJ-22
Reverse PID3 deviation
PID target
value
Feedback
value
・PID3 deviation can be reversed.
Code/Name
AJ-23
PID3 unit selection
AJ-24
PID3 scaling (0%)
AJ-25
PID3 scaling (100%)
AJ-26
PID3 scaling (decimal
point)
・You can switch the display data and the display unit
involved in the output of the PID control by the
calculation.
Code/Name
AJ-27
Target value reference
selection for PID3
AJ-30
PID3 target value
・When PID3 target value input is selected, if the selected
is the parameter setting, [AJ-30] gets enabled.
Code/Name
AJ-32
Feedback data
reference selection for PID3
・Selects the PID3 feedback reference.
*1)00(Not used)/01(Ai1 terminal)/02(Ai2 terminal)/03(Ai3 terminal)/
04(Ai4 terminal)/05(Ai5 terminal)/06(Ai6 terminal)/07(Parameter)/
08(RS485)/ 12(Pulse train input: main)/ 13(Pulse train input:
option)/15(PID1 output)
4-26
[AJ-21]~[AJ-30]
Range (unit)
00(Disable)/01(Enable)/
02(Enable:inverted output)
Range (unit)
00(Disable)/
01(Enable)
Reverse PID3
+
[AJ-22]
-
00
01
-
+
Range (unit)
<unit table> at the end
of the document can
be consulted
-10000~10000
-10000~10000
0~4
Range (unit)
00~08, 12, 13, 15 *1)
-100.00~100.00(%)
Range (unit)
00~08, 12, 13, 15 *1)
Initial
value
00
Initial value
00
PID
operation
Initial
value
03
0
10000
2
Initial
value
07
0.00
Initial
value
02