Hitachi P1-00080-L Basic Manual page 83

Sj series
Hide thumbs Also See for P1-00080-L:
Table of Contents

Advertisement

Chapter 4
[CA-01]~[CA-31]
■Parameter mode (C code)
Input terminal settings
Code/Name
CA-01
Input terminal [1]
CA-02
Input terminal [2]
CA-03
Input terminal [3]
CA-04
Input terminal [4]
CA-05
Input terminal [5]
CA-06
Input terminal [6]
CA-07
Input terminal [7]
CA-08
Input terminal [8]
CA-09
Input terminal [9]
CA-10
Input terminal [A]
CA-11
Input terminal [B]
・The functions for the input terminals 1~9,A,B are
assigned in [CA-01]~[CA-09],[CA-10],[CA-11].
Input terminal NO/NC settings
Code/Name
CA-21
Input terminal [1] active state
CA-22
Input terminal [2] active state
CA-23
Input terminal [3] active state
CA-24
Input terminal [4] active state
CA-25
Input terminal [5] active state
CA-26
Input terminal [6] active state
CA-27
Input terminal [7] active state
CA-28
Input terminal [8] active state
CA-29
Input terminal [9] active state
CA-30
Input terminal [A] active state
CA-31
Input terminal [B] active state
・The functions for the Intelligent input terminals 1~
9,A,B are assigned in [CA-21]~[CA-29],[CA-30],[CA-31].
・However, in the case of [RS] assignment the NO/NC will
not apply, only NO will apply.
Initial
Range (unit)
value
028
015
029
Reference
<Input terminal
032
function list>
031
103 [PLA] Pulse train
003
input A is restricted to
[CA-10],
004
104 [PLB] Pulse train
002
input B is restricted to
001
[CA-11],
033
034
Initial
Range (unit)
value
00
00
00
00
00
00(Normally
Open: NO)/
00
01(Normally
Closed: NC)
00
00
00
00
00
For parameter configuration
Output terminal chatter prevention
Code/Name
CA-41
Input terminal [1] response time
CA-42
Input terminal [2] response time
CA-43
Input terminal [3] response time
CA-44
Input terminal [4] response time
CA-45
Input terminal [5] response time
CA-46
Input terminal [6] response time
CA-47
Input terminal [7] response time
CA-48
Input terminal [8] response time
CA-49
Input terminal [9] response time
CA-50
Input terminal [A] response time
CA-51
Input terminal [B] response time
・Sets the time to wait after the input change has ended,
and for the input to become stable and responsive.
Time allowed in simultaneous terminal change
Code/Name
CA-55
Multistage input settlement
time
・Sets the dead time for multistage speed and position
terminals change.
4-35
[CA-41]~[CA-55]
Range
Initial
(unit)
value
2
2
2
2
2
0~400(ms)
2
2
2
2
2
2
Initial
Range (unit)
value
0
0~2000(ms)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents