This chapter describes basic settings, frequency source
required for operation, examples of run command
source settings and examples of adjusted I/O terminals.
 Basic settings 1
3.1 Set the load rating
Select [Ub-03] load specification selection on the
parameter setting screen.
STOP
Ub-03
Load type selection
00 V-Low Duty
01 Low Duty
02 Normal Duty
Menu
oFW
When [Ub-03] is changed, the parameters set for the
current are automatically adjusted in proportion to the
changed rated current, and the set values are changed.
If the current is set using overload restriction,
electronic
thermal
reconfirmation
is
specification selection is set first.
 Parameter
Parameter
Details
Select the load
[Ub-03]
specification.
*) The underlined value is set by default.
M1
H03
60.00
Option
and
warning
functions,
required;
therefore
Setting data
00: V-Low Duty (VLD)
01: Low Duty (LD)
02: Normal Duty (ND)
Operation Setting and Examples of I/O Adjustment
See "Chapter 4 Settings" for detailed operating
instructions
 Basic settings 2
3.2 Set the motor data
Set the parameters listed in the table below on the
parameter setting screen according to the motor you
use (e.g. induction motor and permanent-magnet
motor).
STOP
AA121
Control mode_M1
0
VFC-VC
1
VFC-VP
2
VFC-FREE
3
VFC-A.bst
Menu
 Parameter
Induction motor (IM)
Parameter
Details
[AA121]
Control pulse setting
[Hb102]
Capacity selection
[Hb103]
Motor poles setting
[Hb104]
Base frequency
Load
[Hb105]
Maximum frequency
[Hb106]
Rated voltage
[Hb108]
Rated current
Synchronous motor (permanent-magnet motor)
(SM(PMM))
Parameter
Details
[AA121]
Control pulse setting
[Hd102]
Capacity selection
[Hd103]
Motor poles setting
[Hd104]
Base frequency
[Hd105]
Maximum frequency
[Hd106]
Rated voltage
[Hd108]
Rated current
Note: Motor constant setting is required for driving SM.
3-1
M1
60.00
oFW
Option
Setting data
00: V/f control constant
torque characteristic , etc.
0.01 to 630.00 (kW)
2 to 48 (poles)
10.00 to 590.00 (Hz)
10.00 to 590.00 (Hz)
1 to 1000 (V)
0.01 to 9999.99 (A)
Setting data
09: PM motor
0.01 to 630.00 (kW)
2 to 48 (poles)
10.00 to 590.00 (Hz)
10.00 to 590.00 (Hz)
1 to 1000 (V)
0.01 to 9999.99 (A)