Chapter 4
[AH-01]~[AH-06]
PID1 function
Code/Name
AH-01
PID1 enable
02(Enable:inverted output)
・Validates the PID1 operation.
・If [AH-01]=01 when the PID output reaches negative
value, the PID output is limited to 0.
・If [AH-01]=02 when the PID output reaches negative
value, the PID output lets out an inverted output.
・When the PID output is negative, the motor will rotate
in the contrary direction.
・If [PID] terminal is ON, the PID control is disabled and
the [PID] target value becomes the frequency
reference.
Code/Name
AH-02
Reverse PID1 deviation
+
PID target value
-
Feedback
+
Code/Name
AH-03
PID1 unit selection
AH-04
PID1 scaling (0%)
AH-05
PID1 scaling (100%)
AH-06
PID1 scaling (decimal
point)
・The unit and display data related to the output of the
PID control can be changed.
Multistage target 1~15
09
PID1 target [AH-10]
01
Analogue input 1
02
[AH-07]
Analogue input 2
03
Analogue input 3
10
RS485
communication
11
Option 1
12
[AH-42]
Option 2
13
Option 3
PID1 target [AH-44] 09
00
Not used
Range (unit)
Initial value
00(Disable)/
01(Enable)/
00
Range (unit)
Initial value
00(Disable)/
00
01(Enable)
Reverse PID1
[AH-02]
-
00
PID
01
operation
Initial
Range (unit)
value
<unit table> at the end
of the document can
03
be consulted
-10000~10000
-10000~10000
10000
0~4
PID1
target value
[SVC1-4]
01
[AH-50]
+, -, x, ÷
00
For parameter configuration
Code/Name
AH-07
Target value 1 reference
selection for PID1
AH-10
PID1 target value-1
AH-12
PID1 Multistage target value 1
AH-14
PID1 Multistage target value 2
AH-16
PID1 Multistage target value 3
AH-18
PID1 Multistage target value 4
AH-20
PID1 Multistage target value 5
AH-22
PID1 Multistage target value 6
AH-24
PID1 Multistage target value 7
AH-26
PID1 Multistage target value 8
AH-28
PID1 Multistage target value 9
AH-30
PID1 Multistage target value 10
AH-32
PID1 Multistage target value 11
AH-34
PID1 Multistage target value 12
AH-36
PID1 Multistage target value 13
AH-38
PID1 Multistage target value 14
AH-40
PID1 Multistage target value 15
AH-42
Target value 2 reference
selection for PID1
AH-44
PID1 target value-2
AH-46
Target value 3 reference
selection for PID1
AH-48
PID1 target value-3
AH-50
Math operator selection of
0
PID1 target value 1
*1) Display range can be set by [AH-04], [AH-05] and [AH-06].
*2) 00(Disabled)/01(Ai1 terminal)/02(Ai2 terminal)/
2
03(Ai3 terminal)/07(Parameter)/08(RS485)/14(Pulse train
input:main)/
・For PID1 target value, two targets are selected, target value 1 and
target value 2, the result of the operation carried out between these
two targets constitutes the PID1 target value.
・If Input terminal function 051[SVC1]~054[SVC4] are used, the PID
target value can be changed for the Multistage.
Multistage value
Target value 0
Target value 1
Target value 2
Target value 3
Target value 4
Target value 5
Target value 6
Target value 7
Target value 8
Target value 9
Target value 10
Target value 11
Target value 12
Target value 13
Target value 14
Target value 15
4-22
[AH-07]~[AH-50]
Range (unit)
00~06/09~15
*1)
0.00~100.00(%)
*1)
00~13*2)
0.00~100.00(%)
00~13*2)
0.00~100.00(%)
01(Addition)
02(Subtraction)
03(Multiplication)
04(Division)
SVC4
SVC3
SVC2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
Initial
value
09
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
00
0.00
0.00
0.00
01
SVC1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON