Hitachi P1-00080-L Basic Manual page 29

Sj series
Hide thumbs Also See for P1-00080-L:
Table of Contents

Advertisement

Chapter 2
 400V class
• For ND rating
Model
Applicable
P1-*******
Motor
(P1-****)
(kW)
P1-00041-H(P1-007H)
0.75
P1-00054-H(P1-015H)
1.5
P1-00083-H(P1-022H)
2.2
P1-00126-H(P1-037H)
3.7
P1-00175-H(P1-055H)
5.5
P1-00250-H(P1-075H)
7.5
P1-00310-H(P1-110H)
11
P1-00400-H(P1-150H)
15
P1-00470-H(P1-185H)
18.5
P1-00620-H(P1-220H)
22
P1-00770-H(P1-300H)
30
P1-00930-H(P1-370H)
37
P1-01160-H(P1-450H)
45
P1-01470-H(P1-550H)
55
P1-01760-H(P1-750H)
75
P1-02130-H(P1-900H)
90
P1-02520-H(P1-1100H)
110
P1-03160-H(P1-1320H)
132
• For LD/VLD rating
Model
Applicable
P1-*******
Motor
(P1-****)
(kW)
P1-00041-H(P1-007H)
1.5
P1-00054-H(P1-015H)
2.2
P1-00083-H(P1-022H)
3.7
P1-00126-H(P1-037H)
5.5
P1-00175-H(P1-055H)
7.5
P1-00250-H(P1-075H)
11
P1-00310-H(P1-110H)
15
P1-00400-H(P1-150H)
18.5
P1-00470-H(P1-185H)
22
P1-00620-H(P1-220H)
30
P1-00770-H(P1-300H)
37
P1-00930-H(P1-370H)
45
P1-01160-H(P1-450H)
55
P1-01470-H(P1-550H)
75
P1-01760-H(P1-750H)
90
P1-02130-H(P1-900H)
110
P1-02520-H(P1-1100H)
132
P1-03160-H(P1-1320H)
160
 Device model name on above table shows example selection. The
device selection should be made in base on rated current, short
circuit current capability and accordance to the local electrical
legislation.
 Applicable motor capacity is based on Hitachi 400Vac, 60Hz, 4 pole
IE3 motor.
 Refer to the wire gauge table on chapter 2-8.
Applicable devices (Input Voltage 400~440V)
Without reactor
(DCL or ACL)
Earth-leakage breaker
Magnetic Contactor
(ELB)
Example
Current
AC-1
model
Rate
EX50C
5
HS8
EX50C
10
HS8
EX50C
10
HS8
EXK50-C
15
HS8
EXK50-C
20
HS8
EXK50-C
30
HS8
EXK50-C
40
HS20
EXK50-C
50
HS25
EXK100-C
75
HS35
EXK100-C
75
HS50
EXK100-C
100
HS50
RXK125-S
125
H80C
EXK225
150
H80C
EXK225
200
H100C
RXK250-S
250
H150C
EX400
300
H200C
EX400
400
H200C
EX600B
500
H250C
Applicable devices (Input Voltage 400~440V)
Without reactor
(DCL or ACL)
Earth-leakage breaker
Magnetic Contactor
(ELB)
Example
Current
AC-1
model
Rate
EX50C
10
HS8
EX50C
10
HS8
EXK50-C
15
HS8
EXK50-C
20
HS8
EXK50-C
30
HS8
EXK50-C
40
HS20
EXK50-C
50
HS25
EXK100-C
75
HS35
EXK100-C
75
HS50
EXK100-C
100
HS50
RXK125-S
125
H80C
EXK225
150
H80C
EXK225
200
H100C
EX400
250
H150C
EX400
300
H200C
EX400
400
H200C
EX600B
500
H250C
EX600B
600
H400C
2-11
Earth-leakage breaker
(MC)
(ELB)
Example
AC-3
model
HS8
EX50C
HS8
EX50C
HS8
EX50C
HS10
EX50C
HS20
EXK50-C
HS25
EXK50-C
HS35
EXK50-C
HS50
EXK50-C
HS50
EXK50-C
H65C
EXK60-C
H80C
EXK100-C
H100C
EXK100-C
H125C
RXK125-S
H125C
EXK225
H200C
EXK225
H250C
EXK225
H300C
EX400
H300C
EX400
Earth-leakage breaker
(MC)
(ELB)
Example
AC-3
model
HS8
EX50C
HS8
EX50C
HS10
EX50C
HS20
EXK50-C
HS25
EXK50-C
HS35
EXK50-C
HS50
EXK50-C
HS50
EXK50-C
H65C
EXK60-C
H80C
EXK100-C
H100C
EXK100-C
H125C
RXK125-S
H125C
EXK225
H200C
EXK225
H250C
EXK225
H300C
EX400
H300C
EX400
H400C
EX400
 Electrical endurance for AC-1 magnetic contactor is 500000 times,
however, for emergency stop in motor operation will be only 25
times.
 Select AC-3 class magnetic contactor for inverter output for
application which has an emergency stop or commercial power line
operation.
 When selecting oversize inverter capacity compare to motor rating,
select according to the inverter capacity
Installation and Wiring
With reactor
(DCL or ACL)
Magnetic Contactor
(MC)
Current
AC-1
Rate
5
HS8
5
HS8
10
HS8
10
HS8
HS10
15
HS8
HS20
20
HS20
HS25
30
HS25
HS35
40
HS35
HS50
50
HS50
HS50
60
HS50
H65C
75
H80C
H80C
100
H80C
H100C
125
H100C
H125C
150
H150C
H125C
200
H200C
H200C
225
H200C
H250C
300
H250C
H300C
350
H400C
H400C
With reactor
(DCL or ACL)
Magnetic Contactor
(MC)
Current
AC-1
Rate
5
HS8
10
HS8
10
HS8
15
HS8
HS20
20
HS8
HS20
30
HS8
HS25
40
HS20
HS35
50
HS20
HS35
60
HS35
HS50
75
HS50
H65C
100
HS50
H65C
125
H65C
H80C
150
H80C
H100C
200
H100C
H125C
225
H125C
H150C
300
H150C
H250C
350
H200C
H250C
400
H250C
H300C
AC-3
HS8
HS8
HS8
AC-3
HS8
HS8
HS8