Hitachi P1-00080-L Basic Manual page 42

Sj series
Hide thumbs Also See for P1-00080-L:
Table of Contents

Advertisement

Chapter 2
Operational
No.
Work
phase
12
Installation
Wiring
(a)
12
Installation
Wiring
(b)
12
(c)
Installation
Wiring
12
Use
Wiring
(d)
Maintenance
Inspection
12
(e)
Use
Setting
Maintenance
13 Use
Operation
14 General
General
The installation, wiring and setting work must be
conducted by qualified engineers.
Residual
Part
Details of harm or damage
risk
Motor insulation damage due to surge
DANGER
caused by long distance motor wiring.
Motor damage due to insulation failure
DANGER
caused by motor voltage unmatched.
Motor damage due to unstable power
supply, caused by power supply
DANGER
unbalance, low voltage or excessive
voltage drop.
Motor damage due to continue ran in
-
DANGER
open phase on motor output line.
Motor damage due high current on motor
DANGER
caused by inadequate parameter setting.
The motor once stopped runs
(C)
DANGER
automatically.
Damage or injury occurrence from a
DANGER
hidden risk.
When the motor wiring distance exceeds
20m or more, try to shorten the wiring.
Use LCR filter or output AC reactor.
Use motor according to the inverter
voltage class.
Confirm the inverter power supply
voltage, feeding method and capacity.
Verify the motor output line that not
being in open phase.
Set adequate value for related function
parameter of motor electronic thermal
level [bC-01] to [bC125].
Set adequate value for base frequency,
motor rated current, control mode,
motor constant, load rating, direct
current output related parameters.
(representative parameter)
Motor related parameter:
IM: [Hb102] to [Hb118]
SM(PMM): [Hd102] to [Hd118]
Control mode: [AA121]
Load rating: [Ub-03]
DC braking: [AF101] to [AF109]
If automatic restart after motor stop is set
by a function, make sure to clearly
describe that in the system.
Confirm that system is structured for fail
safe considering a risk assessment.
For using [SET] function of input terminal, similarly, set the
nd
related 2
parameters settings.
2-24