Installation and Operating Manual
NOTIFIER ITA
a Pittway Company
M-131.1-CFP600-ENG
Document:
07/1999
Issue :
CFP-600-E
LIA
B.1
Rev.:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CFP-600-E and is the answer not in the manual?

Questions and answers

Summary of Contents for Notifier CFP-600-E

  • Page 1: Control Panel

    M-131.1-CFP600-ENG Document: 07/1999 Issue : Rev.: 12-Zone Conventional CFP-600-E Control Panel Complies with EN54.2 Installation and Operating Manual NOTIFIER ITA a Pittway Company...
  • Page 2: Installation Precautions

    System inspection and testing should be scheduled monthly or as required by National and/or lo- cal fire codes. Adequate written records of all inspections should be kept. INDEX.VP Installation and Operating Manual Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 3: Table Of Contents

    Programming the CBE Equation Change Service Enabling Status Change Zone parameters Change Verification Times Programming the Relay mapping (on optional 16- relay board) Enabling the Relay Signal Silence (on optional 16-relay board) INDEX.VP Installation and Operating Manual Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 4 APPENDIX B Menu Item list INSTALLATION Control Panel Internal view Cabinet dimensions and wall-mounting instructions Control Panel Wiring Optional Boards 16-relay optional board 2-release channel optional board Electrical Features GLOSSARY Installation and Operating Manual INDEX.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 5: Keypad & Led Indicators

    Key to leave alarm display. N.B. : Reset, Control Silence and Buzzer Silence, are not allowed during alarm acknowledgement. Reset is allowed only after carring out all event acknowledgement. CFP-600-Prog-1.VP Installation and Operating Manual Page 1 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 6: Control Silence - Silenced Control Reset - Evacuation

    This key clears all Alarms or Troubles in the system. » N.B.:reset is allowed only after all event (Alarms or Troubles) acknowledgement. In order to reset the events, the operator has to know LEVEL 1 PASSWORD. Page 2 Installation and Operating Manual CFP-600-Prog-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 7: Entering Passwords

    (Enabling Function Menu), has not been programmed, it is not possible to Modify Exit|E00 modify the release channel enabling. At the power ON of the control panel the release channels are disabled. CFP-600-Prog-1.VP Installation and Operating Manual Page 3 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 8: Display Zone Status

    |E00 • DISABLED = Included Zone but Disabled, without Troubles • EXCLUDED = Excluded Zone CURSOR KEYS To select another zone use Press to leave this function. Page 4 Installation and Operating Manual CFP-600-Prog-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 9: Change Zones - Enable/Disable Status

    Historicl Log Function to the zone » NOTE: Historical Log may store maximum 50 events. To display the Historical Log, enter the Level 2 PASSWORD. CFP-600-Prog-1.VP Installation and Operating Manual Page 5 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 10: Change Prealarm Recognition Time (Level 3 Password Required)

    | D00 to program date and time. ENTER key CURSOR KEYS 01-01-97 00:48| E00 Date Time » NOTE: enter the Level 3 PASSWORD to program date and time. Page 6 Installation and Operating Manual CFP-600-Prog-2.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 11: Change Level 1 Password

    Walk Test. Press to leave this function. Anyway, the control panel will escape this function after a maximum programmable time-out (see SYSTEM TIME DELAY) CFP-600-Prog-2.VP Installation and Operating Manual Page 7 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 12: Change Controls - Enable/Disable Status

    , it is possible to display the Software Revision Number installed on the control panel. ENTER Will you please always quote this number for your assistance requests. Press to go back to the main screen. Page 8 Installation and Operating Manual CFP-600-Prog-2.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 13: Change Level 2 Password

    PROGRAMMING THE SYSTEM NAME • CLEARING THE CONTROL PANEL MEMORY • CHANGE LANGUAGE DISPLAY • CHANGE ALL LEVEL PASSWORDS Press to go back to the main screen. CFP-600-Prog-2.VP Installation and Operating Manual Page 9 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 14: Change Zones - Include/Exclude Status

    Zone nr. 2 in Pre-Alarm status 02 P EQUATION CONFIGURATION › Phase A) EQUATION for Z. _ EQUATION for Z.2_ EQUATION for Z. 20 • • • Page 10 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 15: Change Service Enabling Status

    ENTER REMOTE RESET |A08 REMOTE RESET |A08 REMOTE RESET |A08 ENABLING |G08 ENABLING |G08 ENABLING |G08 |D00 |D00 |D00 Modify Exit |E00 |E00 Modify Exit |E00 ENTER CFP-600-Prog-3.VP Installation and Operating Manual Page 11 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 16: Change Zone Parameters

    CONFIGURATION |G08 ENTER |D00 |E00 CURSOR VERIF. TIMES |A08 ENTER Z. __ |G08 |D00 |E00 VERIF. TIMES Z. 01 ENTER VERIF. TIMES CURSOR ENTER Z. 01 0’’ Page 12 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 17: Programming The Relay Mapping (On Optional 16-Relay Board)

    ENTER | D00 | E00 R. __ | A00 CURSOR | G00 | D00 ENTER | E00 R. 02 |A08 SILENCEABLE |G08 ENTER |D00 Modify Exit |E00 CFP-600-Prog-3.VP Installation and Operating Manual Page 13 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 18: Change Zone Description

    | E00 CURSOR MAX SYSTEM TIME | A00 IN DAY MODE | G00 ENTER | D00 | E00 » NOTE: The programming time cannot exceed 18 hours. Page 14 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 19: Change Alarm Time Parameter

    0/1 values, then press to confirm the programming. CURSOR ENTER The same as for the other functions, press key to leave the function without changing the existing programming. CFP-600-Prog-4.VP Installation and Operating Manual Page 15 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 20: Programming The Release Zone Mapping

    The display shows the first function available. |D00 |E00 Press keys to select the desired function. CURSOR TROUBLE |A08 HISTORICAL LOG |G08 |D00 Press to change the programming. ENTER Modify Exit |E00 Page 16 Installation and Operating Manual CFP-600-Prog-4.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 21: Programming The System Name

    6:D = GERMAN 6:RO = ROMANIAN • • 7:SV= SWEDISH = CROATIAN » On request, it is also available a Software Version in ENGLISH and RUSSIAN CYRILLIC characters. CFP-600-Prog-4.VP Installation and Operating Manual Page 17 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 22: Change All Level Passwords

    CURSOR ENTER LEV.3 PASSW.__ |G08 0003 |D00 Press again to accomplish the programming. ENTER |E00 Press if you DO NOT WANT to modify the programming. Page 18 Installation and Operating Manual CFP-600-Prog-4.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 23: Appendix A

    DISPLAY= 01: ZXX AL CONTROL TIMINGS EXPIRED ALARM LED= ON ALARM RELAY= OFF SOUNDER RELAY= OFF BUZZER= SILENT SIGNAL SILENCE LED SIGNAL SILENCE DISPLAY= 01: ZXX AL = ON CFP-600-Prog-5.VP Installation and Operating Manual Page 19 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 24: Automatic Release Channel Management

    TROUBLE LED= FLASHING TROUBLE LED= ON TROUBLE RELAY= ON BUZZER= INTERMITTENT SOUND BUZZER= INTERMITTENT SOUND » WAITING FOR RESET NOTE: In “battery trouble” condition the release never occurs. Page 20 Installation and Operating Manual CFP-600-Prog-5.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 25: Doc. M-131.1-Cfp600-Eng Rev

    Alarm Time Sounder Control Activation Time Walk-Test and Line test max Time 2nd Alarm Waiting Time Evacuation Time Release Actuation Time Release Repetition Troubles Reset Configuration Test Mode CFP-600-Prog-5.VP Installation and Operating Manual Page 21 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 26: Installation

    Invert the procedure to close the panel DIMENSIONS A: 388 mm. B: 305 mm. C: 125 mm. 4 fixing back holes: diam. 7.9 mm. (wheel-base 243x319 mm.) Page 22 Installation and Operating Manual CFP-600-Instal-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 27: Control Panel Wiring

    CFP-600-E Control Panel Wiring 24V RESETTABLE OUTPUT for ancillary devices External Power Supply Input 24 VDC Nominals MAINS FUSE 5 x 20 1 A 2 X BATTERIES ( 12V , 6Ah Max.) 24V NOT RESETTABLE OUTPUT for ancillary devices 220 VAC MAINS...
  • Page 28: Optional Boards

    OPTIONAL BOARDS Cabinet slide to fix the boards Spacer to fix the board CFP-600-E Control Panel Main card Release board T I V T I V - 9 3 - 9 3 - 0 8 - 0 8 Spacers to fix the board...
  • Page 29: Release Channel Optional Board

    Channel 1 evacuation relay SHIELDED CABLE Channel 2 evacuation relay RELEASE 2 CARTRIDGE Channel 1 Release output OUTPUT 10-Ohm- 1 W End of Line resistor Channel 2 Release output Page 25 Installation and Operating Manual CFP-600-Instal-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
  • Page 30: Electrical Features

    Prealarm= 1 SPDT switch - 24 VDC - 1 A resistive. Trouble= 1 SPDT switch - 24 VDC - 1 A resistive. Sounders= 1 supervised contact 24 VDC - 1 A resistive. CFP-600-Instal-1.VP Installation and Operating Manual Page 26 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 31: Glossary

    RESET: manual operation which allows in case of zone alarm to silence the buzzer and the not silenceable alarm outputs as well as allows to clear the alarms on the display. Page 27 Installation and Operating Manual CFP-600-Gloss-E.VP NOTIFIER ITALIA Rev. B.1 Doc. M.131.1-CFP600-ENG...
  • Page 32 DO NOT CARE ACTIVATED DO NOT CARE = NOT INHIBITED DO NOT CARE ACTIVATED DO NOT CARE = INHIBITED » NOTE: In “Battery trouble condition” the release NEVER occurs. CFP-600-Gloss-E.VP Installation and Operating Manual Page 28 Doc. M.131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
  • Page 33 Document: 07/1999 Issue : Rev.: All rights reserved. All specifications are subject to change without notice. Delivery times depend on product availability. NOTIFIER ITALIA S.r.l. Via Grandi, 22 - 20097 San Donato Milanese (MI) Tel.: 02/51897.1 (ISDN) Fax: 02/5189730 http://www.notifier.it...