M-131.1-CFP600-ENG Document: 07/1999 Issue : Rev.: 12-Zone Conventional CFP-600-E Control Panel Complies with EN54.2 Installation and Operating Manual NOTIFIER ITA a Pittway Company...
System inspection and testing should be scheduled monthly or as required by National and/or lo- cal fire codes. Adequate written records of all inspections should be kept. INDEX.VP Installation and Operating Manual Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
Programming the CBE Equation Change Service Enabling Status Change Zone parameters Change Verification Times Programming the Relay mapping (on optional 16- relay board) Enabling the Relay Signal Silence (on optional 16-relay board) INDEX.VP Installation and Operating Manual Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
Page 4
APPENDIX B Menu Item list INSTALLATION Control Panel Internal view Cabinet dimensions and wall-mounting instructions Control Panel Wiring Optional Boards 16-relay optional board 2-release channel optional board Electrical Features GLOSSARY Installation and Operating Manual INDEX.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
Key to leave alarm display. N.B. : Reset, Control Silence and Buzzer Silence, are not allowed during alarm acknowledgement. Reset is allowed only after carring out all event acknowledgement. CFP-600-Prog-1.VP Installation and Operating Manual Page 1 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
This key clears all Alarms or Troubles in the system. » N.B.:reset is allowed only after all event (Alarms or Troubles) acknowledgement. In order to reset the events, the operator has to know LEVEL 1 PASSWORD. Page 2 Installation and Operating Manual CFP-600-Prog-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
(Enabling Function Menu), has not been programmed, it is not possible to Modify Exit|E00 modify the release channel enabling. At the power ON of the control panel the release channels are disabled. CFP-600-Prog-1.VP Installation and Operating Manual Page 3 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
|E00 • DISABLED = Included Zone but Disabled, without Troubles • EXCLUDED = Excluded Zone CURSOR KEYS To select another zone use Press to leave this function. Page 4 Installation and Operating Manual CFP-600-Prog-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
Historicl Log Function to the zone » NOTE: Historical Log may store maximum 50 events. To display the Historical Log, enter the Level 2 PASSWORD. CFP-600-Prog-1.VP Installation and Operating Manual Page 5 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
| D00 to program date and time. ENTER key CURSOR KEYS 01-01-97 00:48| E00 Date Time » NOTE: enter the Level 3 PASSWORD to program date and time. Page 6 Installation and Operating Manual CFP-600-Prog-2.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
Walk Test. Press to leave this function. Anyway, the control panel will escape this function after a maximum programmable time-out (see SYSTEM TIME DELAY) CFP-600-Prog-2.VP Installation and Operating Manual Page 7 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
, it is possible to display the Software Revision Number installed on the control panel. ENTER Will you please always quote this number for your assistance requests. Press to go back to the main screen. Page 8 Installation and Operating Manual CFP-600-Prog-2.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
PROGRAMMING THE SYSTEM NAME • CLEARING THE CONTROL PANEL MEMORY • CHANGE LANGUAGE DISPLAY • CHANGE ALL LEVEL PASSWORDS Press to go back to the main screen. CFP-600-Prog-2.VP Installation and Operating Manual Page 9 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
Zone nr. 2 in Pre-Alarm status 02 P EQUATION CONFIGURATION › Phase A) EQUATION for Z. _ EQUATION for Z.2_ EQUATION for Z. 20 • • • Page 10 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
CONFIGURATION |G08 ENTER |D00 |E00 CURSOR VERIF. TIMES |A08 ENTER Z. __ |G08 |D00 |E00 VERIF. TIMES Z. 01 ENTER VERIF. TIMES CURSOR ENTER Z. 01 0 Page 12 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
| E00 CURSOR MAX SYSTEM TIME | A00 IN DAY MODE | G00 ENTER | D00 | E00 » NOTE: The programming time cannot exceed 18 hours. Page 14 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
0/1 values, then press to confirm the programming. CURSOR ENTER The same as for the other functions, press key to leave the function without changing the existing programming. CFP-600-Prog-4.VP Installation and Operating Manual Page 15 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
The display shows the first function available. |D00 |E00 Press keys to select the desired function. CURSOR TROUBLE |A08 HISTORICAL LOG |G08 |D00 Press to change the programming. ENTER Modify Exit |E00 Page 16 Installation and Operating Manual CFP-600-Prog-4.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
6:D = GERMAN 6:RO = ROMANIAN • • 7:SV= SWEDISH = CROATIAN » On request, it is also available a Software Version in ENGLISH and RUSSIAN CYRILLIC characters. CFP-600-Prog-4.VP Installation and Operating Manual Page 17 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
CURSOR ENTER LEV.3 PASSW.__ |G08 0003 |D00 Press again to accomplish the programming. ENTER |E00 Press if you DO NOT WANT to modify the programming. Page 18 Installation and Operating Manual CFP-600-Prog-4.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
DISPLAY= 01: ZXX AL CONTROL TIMINGS EXPIRED ALARM LED= ON ALARM RELAY= OFF SOUNDER RELAY= OFF BUZZER= SILENT SIGNAL SILENCE LED SIGNAL SILENCE DISPLAY= 01: ZXX AL = ON CFP-600-Prog-5.VP Installation and Operating Manual Page 19 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
Alarm Time Sounder Control Activation Time Walk-Test and Line test max Time 2nd Alarm Waiting Time Evacuation Time Release Actuation Time Release Repetition Troubles Reset Configuration Test Mode CFP-600-Prog-5.VP Installation and Operating Manual Page 21 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
Invert the procedure to close the panel DIMENSIONS A: 388 mm. B: 305 mm. C: 125 mm. 4 fixing back holes: diam. 7.9 mm. (wheel-base 243x319 mm.) Page 22 Installation and Operating Manual CFP-600-Instal-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG...
OPTIONAL BOARDS Cabinet slide to fix the boards Spacer to fix the board CFP-600-E Control Panel Main card Release board T I V T I V - 9 3 - 9 3 - 0 8 - 0 8 Spacers to fix the board...
RESET: manual operation which allows in case of zone alarm to silence the buzzer and the not silenceable alarm outputs as well as allows to clear the alarms on the display. Page 27 Installation and Operating Manual CFP-600-Gloss-E.VP NOTIFIER ITALIA Rev. B.1 Doc. M.131.1-CFP600-ENG...
Page 32
DO NOT CARE ACTIVATED DO NOT CARE = NOT INHIBITED DO NOT CARE ACTIVATED DO NOT CARE = INHIBITED » NOTE: In “Battery trouble condition” the release NEVER occurs. CFP-600-Gloss-E.VP Installation and Operating Manual Page 28 Doc. M.131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA...
Page 33
Document: 07/1999 Issue : Rev.: All rights reserved. All specifications are subject to change without notice. Delivery times depend on product availability. NOTIFIER ITALIA S.r.l. Via Grandi, 22 - 20097 San Donato Milanese (MI) Tel.: 02/51897.1 (ISDN) Fax: 02/5189730 http://www.notifier.it...