Viewing And Clearing Events - Allen-Bradley PowerFlex 20-COMM-P User Manual

Profibus adapter
Hide thumbs Also See for PowerFlex 20-COMM-P:
Table of Contents

Advertisement

Viewing and Clearing
Events
The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry is put into the
event queue. You can view the event queue with any of these drive
configuration tools:
• LCD PowerFlex 7-Class HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 2.01 or later
• DriveExecutive software, version 1.01 or later
The event queue can contain up to 32 entries. Eventually the event queue
becomes full, because its contents are retained through adapter resets. At
that point, a new entry replaces the oldest entry. Only an event queue clear
operation or adapter power cycle clears the event queue contents.
Resetting the adapter to defaults has no effect on the event queue.
Using the HIM to View and Clear Events
Step
Viewing Events
1. Access parameters in the adapter.
See
Using the PowerFlex 7-Class HIM to Access Parameters on
page
3-2.
key to scroll to Diagnostics.
2. Press the
or
3. Press the
(Enter) key to display the Diagnostics menu in the
adapter.
4. Repeat steps 2 and 3 to enter the Events option and then View
Event Queue option.
5. Press the
or
key to scroll through events.
The most recent event is Event 1.
Clearing Events
1. Access parameters in the adapter.
See
Using the PowerFlex 7-Class HIM to Access Parameters on
page
3-2.
key to scroll to Diagnostics.
2. Press the
or
3. Press the
(Enter) key to display the Diagnostics menu in the
adapter.
4. Repeat steps 2 and 3 to enter the Events option and then the
Clear Event option or Clr Event Queue option.
A message pops up to confirm that you want to clear the message
or queue.
5. Press the
(Enter) key to confirm your request.
If Clr Event Queue was selected, all event queue entries display
'No Event'.
Troubleshooting
Example Screen
Main Menu:
Diagnostics
Parameter
Device Select
Event Q:
1
Ping Time Flt
Dgn: Events
View Event Queue
Clear Event
Clr Event Queue
PowerFlex 20-COMM-P Profibus Adapter User Manual
Publication 20COMM-UM006B-EN-P
7-5
E3