Link Time - Mitsubishi FX3U-USB-BD User Manual

Melsec-f fx series programmable controllers
Hide thumbs Also See for FX3U-USB-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Computer Link
2.2.3

Link time

1. Data transfer
Data transfer
2. Data transfer time
Time to read continuous word devices (timers, counters or data registers) in one station = (21
*2
of read points
data register D8012) in PLC × 3 + Message waiting time
Time to write continuous word devices (timers, counters or data registers) in one station = (20
of written points
data register D8012) in PLC + Message waiting time
*1.
This is the number of characters when the protocol format 1 is used and the sum check is not
provided.
When the protocol format 4 is used, add "4" to this value.
When the sum check is provided, add "4" to this value also.
*2.
The number of points is counted in 1-word units.
3. Time to send or receive one character
The table below shows the time required to send or receive one character when the start bit is 1-bit, the data
length is 7-bit, the parity is 1-bit, and the stop bit is 1-bit.
Transmission speed (baud rate) (bps)
The tables below show the data transfer times depending on the number of continuously read or written word
devices at the transmission speeds of 9600 bps and 19200 bps when the message waiting time is 0 ms
maximum scan time is 20 ms, and the interval time is 100 ms.
<When the transmission speed is 9600 bps> Unit: sec
Number of
data points
10
32
64
When the types of read or written devices increase, "Data transfer time shown in above table × Number of
device types" is required.
When the number of read or written points exceeds "64"
Accordingly, for achieving efficient data transfer, it is recommended to decrease the number of types of
transferred devices and use as many continuous device numbers as possible.
*1.
Available only in FX
*2.
The message waiting time is "0" when the RS-485 interface and two-pair wiring are used.
The message waiting time is "0" also when the RS-232C interface is used.
When one-pair wiring is adopted, a message waiting time of 70 to 150 ms is required for each transfer.
Add this message waiting time.
D-14
Interval time
) × Time to send or receive 1 character (ms) + Interval time + Maximum scan time (special
*2
) × Time to send or receive 1 character (ms) + Interval time + Maximum scan time (special
300
600
1200
2400
4800
9600
19200
*1
38400
Number of stations
1
8
0.3
1.9
0.4
2.6
0.5
3.7
PLC.
3G
Data transfer
Time to send or receive 1 character (ms)
<When the transmission speed is 19200 bps> Unit: sec
Number of
data points
16
3.7
10
5.2
32
7.3
64
*3
, the transfer time increase.
33.34
16.67
8.34
4.17
2.08
1.04
0.52
0.26
Number of stations
1
8
0.2
1.6
0.3
2.0
0.4
2.5
2 Specifications
2.2 Link Specifications
*1
+ 4 × Number
*1
+ 4 × Number
*2
, the
16
3.2
3.9
5.0